2013-08-21 18:31:36 | 700 NORTH DIXIE HIGHWAY - FIRE STATION #7 |
| PERMIT #13080190 |
| MASTER #11120073 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR |
| SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN |
| POSITION. |
| |
| PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT |
| CONNECTION. |
| |
| PROVIDE A 1 ZONE SYSTEM (1 FLOW SWITCH) FOR THE |
| BUILDING. THERE IS NO NEED FOR A SECOND FLOOR SWITCH |
| AND THIS WILL BE MISLEADING IF THERE IS AN OPERATING |
| SECOND FLOOR FLOW SWITCH BECAUSE SEVERAL FIRST FLOOR |
| SPRINKLERS (TRUCK BAYS AND GENERATOR ROOM) ARE BEING |
| SUPPLIED FROM THE SECOND FLOOR EVEN THOUGH THE |
| SPRINKLERS ARE PROTECTING THE FIRST FLOOR. |
| |
| NO SPRINKLER PROTECTION PROVIDED IN TWO SMALL CLOSESTS |
| IN GREAT ROOM #111. |
| |
| NO SPRINKLER PROTECTION PROVIDED AT THE TOP OF THE |
| DUMBWAITER SHAFT. |
| |
| PLANS DO NOT INDICATE THE METHOD (HEAT DETECTOR/FLOW |
| SWITCH WITHOUT TIME DELAY) USED TO SHUNT TRIP POWER TO |
| THE ELEVATOR IN THE EVENT AN AUTOMATIC SPRINKLER |
| ACTIVATES IN THE ELEVATOR MACHINE ROOM. |
| |
| PROVIDE HYDRAULIC CALCULATIONS FOR THE DRY PIPE |
| PREACTION SYSTEM. |
| |
| HYDRAULIC AREA #1 CALCULATES A MAXIMUM OF 3 SPRINKLERS |
| ON AN 1-1/4" BRANCHLINE; HOWEVER, THERE ARE ADJACENT |
| BRANCHLINES WITH AS MUCH AS 6 SPRINKLERS ON A 36 FOOT |
| SECTION OF BRANCHLINE THAT WILL BE MORE HYDRAULICALLY |
| DEMANDING. PROVIDE AN ADDITIONAL REDUCED AREA (1192 |
| SQ.FT.) HYDRAULIC CALCULATION FOR THE UTILITIES CALL |
| TAKER ROOM #3.22 AREA. |
| |