Plan Review Notes
Plan Review Notes For Permit 13080190
Permit Number 13080190
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-08-21 18:31:36700 NORTH DIXIE HIGHWAY - FIRE STATION #7
 PERMIT #13080190
 MASTER #11120073
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR
 SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE A 1 ZONE SYSTEM (1 FLOW SWITCH) FOR THE
 BUILDING. THERE IS NO NEED FOR A SECOND FLOOR SWITCH
 AND THIS WILL BE MISLEADING IF THERE IS AN OPERATING
 SECOND FLOOR FLOW SWITCH BECAUSE SEVERAL FIRST FLOOR
 SPRINKLERS (TRUCK BAYS AND GENERATOR ROOM) ARE BEING
 SUPPLIED FROM THE SECOND FLOOR EVEN THOUGH THE
 SPRINKLERS ARE PROTECTING THE FIRST FLOOR.
  
 NO SPRINKLER PROTECTION PROVIDED IN TWO SMALL CLOSESTS
 IN GREAT ROOM #111.
  
 NO SPRINKLER PROTECTION PROVIDED AT THE TOP OF THE
 DUMBWAITER SHAFT.
  
 PLANS DO NOT INDICATE THE METHOD (HEAT DETECTOR/FLOW
 SWITCH WITHOUT TIME DELAY) USED TO SHUNT TRIP POWER TO
 THE ELEVATOR IN THE EVENT AN AUTOMATIC SPRINKLER
 ACTIVATES IN THE ELEVATOR MACHINE ROOM.
  
 PROVIDE HYDRAULIC CALCULATIONS FOR THE DRY PIPE
 PREACTION SYSTEM.
  
 HYDRAULIC AREA #1 CALCULATES A MAXIMUM OF 3 SPRINKLERS
 ON AN 1-1/4" BRANCHLINE; HOWEVER, THERE ARE ADJACENT
 BRANCHLINES WITH AS MUCH AS 6 SPRINKLERS ON A 36 FOOT
 SECTION OF BRANCHLINE THAT WILL BE MORE HYDRAULICALLY
 DEMANDING. PROVIDE AN ADDITIONAL REDUCED AREA (1192
 SQ.FT.) HYDRAULIC CALCULATION FOR THE UTILITIES CALL
 TAKER ROOM #3.22 AREA.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  