2013-08-05 17:23:36 | WIND LOAD WAS PERFORMED WITHOUT FIXTURES. PROVIDE | | REVISED ENGINEERED WIND LOAD SHOWING THE FIXTURE AND | | ARMS IN PLACE. PLANS AND ENGINEERING DO NOT AGREE FOR | | POLE INSETION DEPTH. | | PROVIDE CLEAR PHOTOMETRICS OF DESIGN TO ENSURE SAFETY | | AND LIGHTING BEYOND THE PROPERTY LINE DOES NOT EXCEED | | .5 FC AND HOW IT WILL BE ACHIEVED IN ACCORDANCE WITH | | THE LISTING OF THE FIXTURE. CLEARLY IDENTIFY POLE | | LOCATIONS AND FIXTURE CONFIGURATION ON PHOTOMETRIC | | PLAN. | | PHOTOMETRICS APPEAR TO DUPLICATE A PREVIOUS REVIEW. | | PLEASE CLARIFY | | PROVIDE LISTING INFORMATION FOR FIXTURES AND ALL | | COMPONENTS | | PROVIDE VOLTAGE DROP CALCS SHOWING COMPLIANCE WITH | | FBC-EC 505.7.3 | | PROVIDE EXTERIOR LIGHTING POWER DENSITY INFORMATION PER | | FBC-EC 505.6 | | PROVIDE TIME CLOCK WITH PROGRAMING BACKUP FOR MINIMUM | | 10 HOURS PER FBC-EC 505.2.4 |
|