Plan Review Notes
Plan Review Notes For Permit 13080146
Permit Number 13080146
Review Stop E
Sequence Number 1
Notes
Date Text
2013-08-05 17:23:36WIND LOAD WAS PERFORMED WITHOUT FIXTURES. PROVIDE
 REVISED ENGINEERED WIND LOAD SHOWING THE FIXTURE AND
 ARMS IN PLACE. PLANS AND ENGINEERING DO NOT AGREE FOR
 POLE INSETION DEPTH.
 PROVIDE CLEAR PHOTOMETRICS OF DESIGN TO ENSURE SAFETY
 AND LIGHTING BEYOND THE PROPERTY LINE DOES NOT EXCEED
 .5 FC AND HOW IT WILL BE ACHIEVED IN ACCORDANCE WITH
 THE LISTING OF THE FIXTURE. CLEARLY IDENTIFY POLE
 LOCATIONS AND FIXTURE CONFIGURATION ON PHOTOMETRIC
 PLAN.
 PHOTOMETRICS APPEAR TO DUPLICATE A PREVIOUS REVIEW.
 PLEASE CLARIFY
 PROVIDE LISTING INFORMATION FOR FIXTURES AND ALL
 COMPONENTS
 PROVIDE VOLTAGE DROP CALCS SHOWING COMPLIANCE WITH
 FBC-EC 505.7.3
 PROVIDE EXTERIOR LIGHTING POWER DENSITY INFORMATION PER
 FBC-EC 505.6
 PROVIDE TIME CLOCK WITH PROGRAMING BACKUP FOR MINIMUM
 10 HOURS PER FBC-EC 505.2.4


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved