Plan Review Notes
Plan Review Notes For Permit 13080144
Permit Number 13080144
Review Stop E
Sequence Number 1
Notes
Date Text
2013-08-05 17:18:29WIND LOAD WAS PERFORMED WITHOUT FIXTURES. PROVIDE
 REVISED ENGINEERED WIND LOAD SHOWING THE FIXTURE AND
 ARMS IN PLACE. PLANS AND ENGINEERING DO NOT AGREE FOR
 POLE INSETION DEPTH.
 PROVIDE CLEAR PHOTOMETRICS OF DESIGN TO ENSURE SAFETY
 AND LIGHTING BEYOND THE PROPERTY LINE DOES NOT EXCEED
 .5 FC AND HOW IT WILL BE ACHIEVED IN ACCORDANCE WITH
 THE LISTING OF THE FIXTURE. CLEARLY IDENTIFY POLE
 LOCATIONS AND FIXTURE CONFIGURATION ON PHOTOMETRIC
 PLAN.
 PROVIDE LISTING INFORMATION FOR FIXTURES AND ALL
 COMPONENTS
 PROVIDE VOLTAGE DROP CALCS SHOWING COMPLIANCE WITH
 FBC-EC 505.7.3
 PROVIDE EXTERIOR LIGHTING POWER DENSITY INFORMATION PER
 FBC-EC 505.6
 PROVIDE TIME CLOCK WITH PROGRAMING BACKUP FOR MINIMUM
 10 HOURS PER FBC-EC 505.2.4