Plan Review Notes For Permit 13080083 |
Permit Number |
13080083 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-09-03 16:30:04 | SERVICE CALCULATION IS NOT PER NEC 220. UNITS HAVE A | | 125A SERVICE AND OVERALL LOAD CALC SHOWS 57.5 A. NO | | HEAT IS PROVIDED. | | PROVIDE DETAILED CUT SHEET ON A/C UNITS SHOWING ACTUAL | | LOAD AND CIRCUIT REQUIRED PER THE LISTING. 110.3, 430, | | 440 | | WIRE SIZES DO NOT MATCH OVERCURRENT PROTECTION - | | 310.15, 310.15, 240.6 | | PROVIDE AIC CALCULATIONS AND/OR VALUES FOR METER CENTER | | AND ELECTRIC LOAD CENTERS. 110. | | PROVIDE ARC FLASH WARNINGS PER 110.26 | | PLANS NOT COMPLETE, ADDITIONAL ITEMS MAY BE NOTED BASED | | ON RESPONSES. |
|