2013-08-06 13:28:55RECEIVED FOR RE-REVIEW ON 9/10/13. THE FOLLOWING NOTES
 ARE ADDED TO THIS SET OF PLANS, NOT TO REPLACE ANY
 PREVIOUS NOTATIONS.
 ADD 3 WAY SWITCH AT OUTSIDE STAIRS. 210.70
 ARC FAULT PROTECTION IS REQUIRED ON THE INDIVIDUAL
 CIRCUITS PER 210.12
 SHOW HEAT IN THE LOAD CALCULATION FOR DETERMINATION OF
 THE LARGEST OF A/C VS HEAT 220.60
 PROVIDE AN OVERALL LOAD CALCULATION ON THE BUILDING FOR
 DETERMINATION OF ACTUAL SERVICE SIZE TO THE BUILDING
 ARTICLE 220
 IT APPEARS MORE A/C UNITS ARE INSTALLED AND CALLED FOR
 THAN SHOWN IN THE LOAD CALCULATION
 DOES NEW 100 AMP PANEL REPRESENT A NEW UNIT?
 WHY IS UNIT "A" SEPARATED FROM THE LAUNDRY ROOM BY A
 RATED WALL WHEN THE ELECTRIC APNEL IS INSTALLED IN THAT
 ROOM?
 PROVIDE LOCATIONS FOR UNITS THAT ARE CALLED OUT ON THE
 LOAD CALCULATION, AS IN WASHER, DRYER FOR EACH UNIT
 SMOKE ALARM MISSING IN UNIT "B"
 PROVIDE GFCI AT REAR PER 210.52E
  
  
  
  
 APPROVED WITH NOTES. MUST MEET ELECTRICAL CODE