Plan Review Notes For Permit 13080072 |
Permit Number |
13080072 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-08-06 13:28:55 | RECEIVED FOR RE-REVIEW ON 9/10/13. THE FOLLOWING NOTES | | ARE ADDED TO THIS SET OF PLANS, NOT TO REPLACE ANY | | PREVIOUS NOTATIONS. | | ADD 3 WAY SWITCH AT OUTSIDE STAIRS. 210.70 | | ARC FAULT PROTECTION IS REQUIRED ON THE INDIVIDUAL | | CIRCUITS PER 210.12 | | SHOW HEAT IN THE LOAD CALCULATION FOR DETERMINATION OF | | THE LARGEST OF A/C VS HEAT 220.60 | | PROVIDE AN OVERALL LOAD CALCULATION ON THE BUILDING FOR | | DETERMINATION OF ACTUAL SERVICE SIZE TO THE BUILDING | | ARTICLE 220 | | IT APPEARS MORE A/C UNITS ARE INSTALLED AND CALLED FOR | | THAN SHOWN IN THE LOAD CALCULATION | | DOES NEW 100 AMP PANEL REPRESENT A NEW UNIT? | | WHY IS UNIT "A" SEPARATED FROM THE LAUNDRY ROOM BY A | | RATED WALL WHEN THE ELECTRIC APNEL IS INSTALLED IN THAT | | ROOM? | | PROVIDE LOCATIONS FOR UNITS THAT ARE CALLED OUT ON THE | | LOAD CALCULATION, AS IN WASHER, DRYER FOR EACH UNIT | | SMOKE ALARM MISSING IN UNIT "B" | | PROVIDE GFCI AT REAR PER 210.52E | | | | | | | | | | APPROVED WITH NOTES. MUST MEET ELECTRICAL CODE |
|