2013-10-28 12:00:24 | THIRD BUILDING REVIEW COMMENTS. |
| |
| 1- TITLE BLOCK FOR SHEETS P-01 AND E-01 HAVE THE NAME |
| OF THE ENGINEER JOHN H. CRESWELL AND THE ARCHITECTS' |
| OFFICE "SSC DESIGN GROUP". ACCORDING TO FLORIDA |
| STATUTES 471 AND 481 ALL SHEETS WITH AN ENGINEER OR |
| ARCHITECT NAME MUST BE SIGNED AND SEALED BY THE |
| LICENSED PROFESSIONAL. OTHERWISE, REMOVE THE NAMES FROM |
| THE TITLE BLOCK AND PROVIDE ONLY THE NAME AND SIGNATURE |
| OF THE PERSON RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1 |
| CITY AMENDMENTS TO FBC. |
| |
| 2- REVISE DETAIL 3 ON SHEET A1. CONCRETE BLOCK WALL |
| INSULATION R-VALUE TO MATCH THE ONE REQUIRED BY THE |
| ENERGY CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| CONSERVATION. |
| |
| 3- ENERGY CALCULATIONS SUBMITTED ARE TAKING THE CEILING |
| FAN CREDIT. SPECIFY ON PLANS CEILING FAN SIZE FOR ALL |
| ROOMS AS REQUIRED BY SEC. 405.6.6 OF 2010 FBC-ENERGY |
| CONSERVATION AND TABLE 405.6.6. (***NOTE: CALCULATIONS |
| ARE DONE FOR THE ENTIRE HOUSE, THEREFORE IF TAKING |
| CEILING FAN CREDIT, THEN ALL THE ROOMS NEED TO HAVE |
| CEILING FANS). |
| |
| 4- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE |
| INSTALLATION OF SHUTTERS. NEED THIS INSTALLATION |
| SCHEDULE TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES |
| OF PRODUCT APPROVAL PROPOSED INSTALLATION AND THE |
| DESIGN PRESSURES REQUIRED BY SEC. R301.2.1.4.3. (REPEAT |
| COMMENT) |
| |
| |
| ***NOTE: PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| |
| |