Plan Review Notes
Plan Review Notes For Permit 13071145
Permit Number 13071145
Review Stop M
Sequence Number 2
Notes
Date Text
2013-09-20 08:32:21RESIDENTIAL (R3) ADDITION/ALTERATION, SECOND MECHANICAL
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- THERE WAS NO A/C INFORMATION SUBMITTED THE FIRST
 TIME, EXCEPT FOR THE 5" FLEX DUCT SHOWN ON SHEET A-06
 TO FEED THE NEW CABANA. CLARIFY SCOPE OF WORK. NOW,
 THERE ARE EQUIPMENT SIZING CALCULATIONS SUBMITTED. WHY
 SUBMITTING THESE CALCULATIONS. IS THERE GOING TO BE AN
 EXACT CHANGE OUT. IF SO, PROVIDE COMPLETE EQUIPMENT
 SIZING CALCULATIONS, NOT JUST THE SUMMARY AND COMPLETE
 THE REQUIRED CHANGE OUT FORMS. IF DOING ANY OTHER
 DUCTWORK, THEN A/C PLANS ARE REQUIRED. SEC.
 107..5.3(10) OF CITY AMENDMENTS TO FBC.
  
 2- PROVIDE SPECIFICATIONS FOR EXHAUST HOOD TO BE
 INSTALLED ABOVE THE GRILL IN THE SUMMER KITCHEN. AND,
 CLARIFY WHERE I S THE HOOD VENTING TO. ELEVATIONS DON'T
 SHOW HOOD VENTING TO THE ROOF. SEC. M1505 OF 2010
 FBC-RESIDENTIAL (REPEAT COMMENT).
  
 3- SPECIFY THE EXHAUST FAN FOR BATHROOM #1 AS REQUIRED
 BY SEC. M1507. ONLY SHOWING EXHAUST FAN AT THE TOILET
 ROOM (REPEAT COMMENT).
  
  
 ****NOTE; PLEASE PROVIDE RESPONSE LETTER ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
  