2013-09-19 13:59:49 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW |
| CHECKLIST. |
| CODE: 2010 FBC. |
| |
| 1- A) ENGINEER OF RECORD SIGNED AND SEALED PLANS ON THE |
| WRONG SPACE IN THE TITLE BLOCK, NOT UNDER HIS NAME AND |
| LICENSE NUMBER SPACE. HE SIGNED THE SPACE FOR "SSC |
| DESIGN GROUP", WHICH IS AN ARCHITECTURAL FIRM THAT |
| DOESN'T HAVE A FLORIDA FIRM LICENSE NUMBER. RESUBMIT |
| DRAWINGS WITH SIGNATURE ON CORRECT SPACE AS REQUIRED BY |
| CHAPTER 471 FLORIDA STATUTE. |
| |
| B) ENGINEER OF RECORD TO SIGN AND SEAL ALL PLANS |
| SUBMITTED AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE. |
| SOME DRAWINGS ARE MISSING THE SEAL AND SIGNATURE. |
| |
| 2- NEED ARCHITECTURAL FIRM FLORIDA LICENSE NUMBER FOR |
| "SSC DESIGN GROUP" AS REQUIRED BY CHAPTER 481 FLORIDA |
| STATUTE. (REPEAT COMMENT). OR REMOVE NAME FROM TITLE |
| BLOCK. |
| |
| 3- REVISE ENERGY CALCULATIONS SUBMITTED. SEC. |
| 103.2.1.1.2 OF 2010 FBC-ENERGY CONSERVATION. |
| A) REVISE THE AREA WEIGHTED AVERAGE OVERHANG DEPTH ON |
| ITEM #7 TO MATCH PLANS (IT'S NOT 2.000FT). |
| |
| B) REVISE ROOF MATERIAL ON PAGE 2 OF 7. THERE ARE NOT |
| SHINGLES ON THE HOUSE. |
| |
| C) REVISE ALL DOORS ON PAGE 4 OF 7 TO MATCH PLANS AND |
| PRODUCT APPROVALS SUBMITTED. REVISE TYPE, SIZE ETC. TO |
| MATCH PLANS. |
| |
| D) REVISE ALL WINDOWS TO MATCH PLANS AND PRODUCT |
| APPROVALS. AND REVISE THE OVERHANG DEPTH AND SEPARATION |
| TO MATCH PLANS. |
| |
| E) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING THE CORRECT BUILDER'S NAME. |
| |
| 4- PROVIDE DETAILS AND SPECIFICATIONS ON PLANS SHOWING |
| HOW OBTAINING R-13 ON CONCRETE BLOCK WALLS FOR INTERIOR |
| AND EXTERIOR WALLS AS SPECIFIED ON THE ENERGY |
| CALCULATIONS SUBMITTED. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| CONSERVATION. |
| |
| 5- ENERGY CALCULATIONS SUBMITTED ARE TAKING THE CEILING |
| FAN CREDIT. SPECIFY ON PLANS CEILING FAN SIZE FOR ALL |
| ROOMS AS REQUIRED BY SEC. 405.6.6 OF 2010 FBC-ENERGY |
| CONSERVATION AND TABLE 405.6.6. |
| |
| 6- REVISE/COORDINATE ALL WINDOW AND DOOR SCHEDULE |
| INFORMATION TO MATCH THE ENERGY CALCULATIONS. MATERIAL |
| TYPE ETC. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. |
| |
| 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) PRECAST LINTELS AS SPECIFIED ON PLANS. NEED 8" |
| PRECAST LINTEL. NOA 13-0321.07 SUBMITTED IS FOR 4", 6" |
| & 12" LINTELS. |
| |
| B) INSWING WOOD DOOR AS SHOWN ON PLANS FOR NEW CABANA |
| BATHROOM. (REPEAT COMMENT). |
| |
| C) ENTRY DOORS THAT MEET THE CALCULATED DESIGN |
| PRESSURES. FLORIDA PRODUCT APPROVAL FL9390-R2 SUBMITTED |
| DOESN'T MEET THE DESIGN PRESSURES. |
| |
| D) WINDOW MULLIONS AS SHOWN ON PLANS. AND SPECIFY SIZE |
| TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES. (REPEAT |
| COMMENT). |
| |
| E)FIXED WINDOWS. NOA 11-1110.15 SUBMITTED WAS |
| SUPERSEDED BY MIAMI-DADE. NEED CURRENT NOA. |
| ***NOTE: ALSO, NEED PRODUCT APPROVAL FOR ALL WINDOW |
| SIZES SHOWN ON PLANS. SEE WINDOW SCHEDULE. (REPEAT |
| COMMENT). |
| |
| 8- ABOVE PRODUCT APPROVALS TO BE REVIEWED AND APPROVED |
| IN WRITING BY THE ENGINEER OF RECORD (NOT SIGNING AND |
| SEALING). SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. |
| |
| 9- SPECIFY CARBON MONOXIDE ALARMS FOR ALL BEDROOM AS |
| REQUIRED BY SEC. R315. (REPEAT COMMENT). |
| |
| 10- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE |
| INSTALLATION OF SHUTTERS. NEED THIS INSTALLATION |
| SCHEDULE TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES |
| OF PRODUCT APPROVAL PROPOSED INSTALLATION AND THE |
| DESIGN PRESSURES REQUIRED BY SEC. R301.2.1.4.3. (REPEAT |
| COMMENT) |
| |
| |
| ***NOTE: PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| |
| |
| ****NOTE: PROVIDE COMPLETE INFORMATION UNDER SEPARATE |
| PERMITS FOR: POOL WORK, NEW GENERATOR, SCREEN ENCLOSURE |
| WORK, GAS WORK, ETC. |
| |