2013-09-19 13:59:49RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- A) ENGINEER OF RECORD SIGNED AND SEALED PLANS ON THE
 WRONG SPACE IN THE TITLE BLOCK, NOT UNDER HIS NAME AND
 LICENSE NUMBER SPACE. HE SIGNED THE SPACE FOR "SSC
 DESIGN GROUP", WHICH IS AN ARCHITECTURAL FIRM THAT
 DOESN'T HAVE A FLORIDA FIRM LICENSE NUMBER. RESUBMIT
 DRAWINGS WITH SIGNATURE ON CORRECT SPACE AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTE.
  
 B) ENGINEER OF RECORD TO SIGN AND SEAL ALL PLANS
 SUBMITTED AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
 SOME DRAWINGS ARE MISSING THE SEAL AND SIGNATURE.
  
 2- NEED ARCHITECTURAL FIRM FLORIDA LICENSE NUMBER FOR
 "SSC DESIGN GROUP" AS REQUIRED BY CHAPTER 481 FLORIDA
 STATUTE. (REPEAT COMMENT). OR REMOVE NAME FROM TITLE
 BLOCK.
  
 3- REVISE ENERGY CALCULATIONS SUBMITTED. SEC.
 103.2.1.1.2 OF 2010 FBC-ENERGY CONSERVATION.
 A) REVISE THE AREA WEIGHTED AVERAGE OVERHANG DEPTH ON
 ITEM #7 TO MATCH PLANS (IT'S NOT 2.000FT).
  
 B) REVISE ROOF MATERIAL ON PAGE 2 OF 7. THERE ARE NOT
 SHINGLES ON THE HOUSE.
  
 C) REVISE ALL DOORS ON PAGE 4 OF 7 TO MATCH PLANS AND
 PRODUCT APPROVALS SUBMITTED. REVISE TYPE, SIZE ETC. TO
 MATCH PLANS.
  
 D) REVISE ALL WINDOWS TO MATCH PLANS AND PRODUCT
 APPROVALS. AND REVISE THE OVERHANG DEPTH AND SEPARATION
 TO MATCH PLANS.
  
 E) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE CORRECT BUILDER'S NAME.
  
 4- PROVIDE DETAILS AND SPECIFICATIONS ON PLANS SHOWING
 HOW OBTAINING R-13 ON CONCRETE BLOCK WALLS FOR INTERIOR
 AND EXTERIOR WALLS AS SPECIFIED ON THE ENERGY
 CALCULATIONS SUBMITTED. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 5- ENERGY CALCULATIONS SUBMITTED ARE TAKING THE CEILING
 FAN CREDIT. SPECIFY ON PLANS CEILING FAN SIZE FOR ALL
 ROOMS AS REQUIRED BY SEC. 405.6.6 OF 2010 FBC-ENERGY
 CONSERVATION AND TABLE 405.6.6.
  
 6- REVISE/COORDINATE ALL WINDOW AND DOOR SCHEDULE
 INFORMATION TO MATCH THE ENERGY CALCULATIONS. MATERIAL
 TYPE ETC. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) PRECAST LINTELS AS SPECIFIED ON PLANS. NEED 8"
 PRECAST LINTEL. NOA 13-0321.07 SUBMITTED IS FOR 4", 6"
 & 12" LINTELS.
  
 B) INSWING WOOD DOOR AS SHOWN ON PLANS FOR NEW CABANA
 BATHROOM. (REPEAT COMMENT).
  
 C) ENTRY DOORS THAT MEET THE CALCULATED DESIGN
 PRESSURES. FLORIDA PRODUCT APPROVAL FL9390-R2 SUBMITTED
 DOESN'T MEET THE DESIGN PRESSURES.
  
 D) WINDOW MULLIONS AS SHOWN ON PLANS. AND SPECIFY SIZE
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES. (REPEAT
 COMMENT).
  
 E)FIXED WINDOWS. NOA 11-1110.15 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. NEED CURRENT NOA.
 ***NOTE: ALSO, NEED PRODUCT APPROVAL FOR ALL WINDOW
 SIZES SHOWN ON PLANS. SEE WINDOW SCHEDULE. (REPEAT
 COMMENT).
  
 8- ABOVE PRODUCT APPROVALS TO BE REVIEWED AND APPROVED
 IN WRITING BY THE ENGINEER OF RECORD (NOT SIGNING AND
 SEALING). SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 9- SPECIFY CARBON MONOXIDE ALARMS FOR ALL BEDROOM AS
 REQUIRED BY SEC. R315. (REPEAT COMMENT).
  
 10- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE
 INSTALLATION OF SHUTTERS. NEED THIS INSTALLATION
 SCHEDULE TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES
 OF PRODUCT APPROVAL PROPOSED INSTALLATION AND THE
 DESIGN PRESSURES REQUIRED BY SEC. R301.2.1.4.3. (REPEAT
 COMMENT)
  
  
 ***NOTE: PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
  
 ****NOTE: PROVIDE COMPLETE INFORMATION UNDER SEPARATE
 PERMITS FOR: POOL WORK, NEW GENERATOR, SCREEN ENCLOSURE
 WORK, GAS WORK, ETC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712