2013-08-22 10:40:03 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- SHEET A0: |
| A) REVISE THE BUILDING EXPOSURE SPECIFIED ON THE |
| "DEVELOPMENT DATA" SPECIFICATIONS. ACCORDING TO SEC. |
| R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL THIS BUILDING IS |
| LOCATED ON EXPOSURE "C" NOT "B". |
| |
| B) REVISE THE WINDOWS/DOORS DESIGN PRESSURES TO |
| CORRESPOND TO EXPOSURE "C". ***NOTE: REVISE PRESSURES |
| ON WINDOW/DOOR SCHEDULES ALSO AND INCLUDE GARAGE DOOR. |
| |
| 2- PLANS TO BE SIGNED AND SEALED BY FLORIDA LICENSED |
| ARCHITECT OR ENGINEER. SEAL STAMPED ON "BASIL |
| IRVING-SSC DESIGN GROUP" IS NOT FROM AN ARCHITECT OR |
| ENGINEER. IT'S A CORPORATE SEAL. CORPORATE SEAL DOESN'T |
| ENTITLE TO PRACTICE ARCHITECTURE OR ENGINEERING. |
| FLORIDA STATUTE 481 AND 471. |
| A) NEED ENGINEER OR ARCHITECT SEAL AND SIGNATURE ON ALL |
| DRAWINGS. CHAPTER 471 OR 481 FLORIDA STATUTE. |
| |
| B) NEED FIRM FLORIDA LICENSE NUMBER FOR "SSC DESIGN |
| GROUP". CHAPTER 481 FLORIDA STATUTE. |
| |
| 3- PROVIDE ENERGY CALCULATIONS. SEC. 101.4.3 OF 2010 |
| FBC-ENERGY CONSERVATION. PLEASE MAKE SURE IS FILLED |
| COMPLETELY AND SIGNED & DATED BY THE OWNER/AGENT ALSO. |
| |
| 4- SHEET A1: REVISE GARAGE SWING DOOR SPECIFICATIONS ON |
| THE DOOR SCHEDULE. NEED TO COMPLY WITH FIRE RATING OF |
| SEC. R302.5.1 OF 2010 FBC-RESIDENTIAL. |
| |
| 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| |
| B) INSWING WOOD DOOR AS SHOWN ON PLANS FOR NEW CABANA |
| BATHROOM. |
| |
| C) GARAGE DOOR FOR SIZE SHOWN ON PLANS. AND, CLARIFY IF |
| REPLACING GARAGE DOORS OR NOT. FLOOR PLAN ON SHEET A2 |
| SAYS "RETAIN EXT OVERHEAD DOOR" AND, SPECIFY THE DESIGN |
| PRESSURES. |
| |
| D) SLIDING GLASS DOORS AS SHOWN ON PLANS. |
| |
| E) FRENCH DOORS AS SHOWN ON PLANS. |
| |
| F) WINDOW MULLIONS AS SHOWN ON PLANS. |
| |
| G) FIXED WINDOWS. NOA 11-1110.15 SUBMITTED WAS |
| SUPERSEDED BY MIAMI-DADE. NEED CURRENT NOA. |
| ***NOTE: ALSO, NEED PRODUCT APRPOVAL FOR ALL WINDOW |
| SIZES SHOWN ON PLANS. SEE WINDOW SCHEDULE. |
| |
| 6- PRODUCT APPROVALS TO BE REVIEWED AND APPROVED IN |
| WRITING BY THE ENGINEER OF RECORD (NOT SIGNING AND |
| SEALING). SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. |
| ***NOTE: PRODUCT APPROVALS HAVE A CORPORATE SEAL. THIS |
| DOESN'T ENTITLE TO PRACTICE ARCHITECTURE OR |
| ENGINEERING. FLORIDA STATUTE 471 AND 481. |
| |
| 7- SPECIFY CARBON MONOXIDE ALARMS FOR ALL BEDROOM AS |
| REQUIRED BY SEC. R315. |
| |
| 8- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE |
| INSTALLATION OF SHUTTERS. NEED THIS INSTALLATION |
| SCHEDULE TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES |
| OF PRODUCT APPROVAL PROPOSED INSTALLATION AND THE |
| DESIGN PRESSURES REQUIRED BY SEC. R301.2.1.4.3. |
| |
| ****NOTE: PROVIDE COMPLETE INFORMATION UNDER SEPARATE |
| PERMITS FOR: POOL WORK, NEW GENERATOR, SCREEN ENCLOSURE |
| WORK, GAS WORK, ETC. |
| |