2013-08-01 07:44:182010 FBC
 170 MPH EXPOSURE B
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF THE PRODUCT APPROVAL FOR THE
 ROOF TILE AND SPECIFY THE TYPE OF ATTACHMENT ATTACHMENT
 THAT WILL BE USED TO INSTALL IT. IF AN ADHESIVE IS USED
 SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR IT. DCA
 RULE 9N-3 AND FBC R301.2.1
  
 2) SUBMIT TWO COPIES OF A DIMENSIONED DIAGRAM OF THE
 ROOF SHOWING THE AREAS WHERE THE REPAIRS ARE BEING
 MADE. FBC EXISTING BUILDING 611.1.1 NOT MORE THAN 25
 PERCENT OF ROOF AREA CAN BE REPAIRED UNLESS THE ENTIRE
 ROOF SYSTEM CONFORMS WITH THIS CODE.
  
 3) THERE IS A CODE VIOLATION ON RECORD FOR ROOFING AND
 STRUCTURAL REPAIRS THAT WERE PREFORMED WITHOUT THE
 PROPER PERMITS. A PENALTY FEE WILL BE ADDED TO THE
 REQUIRED PERMIT FEE.
  