Plan Review Notes
Plan Review Notes For Permit 13071119
Permit Number 13071119
Review Stop B
Sequence Number 1
Notes
Date Text
2013-08-15 15:22:45BUILDING PLAN REVIEW
 PERMIT: 13071119
 ADD: 1617 N FLAGLER DR # 602
 CONT: ED'S ISLAND TIME SERVICES, INC
 TEL: (561)541-0004
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: AUGUST 15, 2010
 ACTION: PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) ID-02 PLANS INDICATE THE USE OF TRIM, NOT SPECIFIED
 IF WOOD OR FOAM.
 2010 FBC-B 806.3 FOAM PLASTIC.
 FOAM PLASTIC USED AS TRIM IN ANY OCCUPANCY SHALL COMPLY
 WITH SECTION 2604.2.
 2604.2 INTERIOR TRIM.
 FOAM PLASTIC USED AS INTERIOR TRIM SHALL COMPLY WITH
 SECTIONS 2604.2.1 THROUGH 2604.2.4.
 [F] 2604.2.1 DENSITY.
 THE MINIMUM DENSITY OF THE INTERIOR TRIM SHALL BE 20
 PCF (320 KG/M3).
 [F] 2604.2.2 THICKNESS.
 THE MAXIMUM THICKNESS OF THE INTERIOR TRIM SHALL BE 1/2
 INCH (12.7 MM) AND THE MAXIMUM WIDTH SHALL BE 8 INCHES
 (204 MM).
 [F] 2604.2.3 AREA LIMITATION.
 THE INTERIOR TRIM SHALL NOT CONSTITUTE MORE THAN 10
 PERCENT OF THE SPECIFIC WALL OR CEILING AREAS TO WHICH
 IT IS ATTACHED.
 [F] 2604.2.4 FLAME SPREAD.
 THE FLAME SPREAD INDEX SHALL NOT EXCEED 75 WHERE TESTED
 IN ACCORDANCE WITH ASTM E 84 OR UL 723. THE
 SMOKE-DEVELOPED INDEX SHALL NOT BE LIMITED.
 EXCEPTION: WHEN THE INTERIOR TRIM MATERIAL HAS BEEN
 TESTED AS AN INTERIOR FINISH IN ACCORDANCE WITH NFPA
 286 AND COMPLIES WITH THE ACCEPTANCE CRITERIA IN
 SECTION 803.1.2.1, IT SHALL NOT BE REQUIRED TO BE
 TESTED FOR FLAME SPREAD INDEX IN ACCORDANCE WITH ASTM E
 84 OR UL 723.
  
 2) A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
 2B) FBC-B 2010 603.2 EXCEPTION (1) TILE FLOORING
 FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
  
 2C) FBC-B 2010 603.2 EXCEPTION 2 WOOD FLOORS
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FBC-B 2010
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]