Plan Review Notes For Permit 13071112 |
Permit Number |
13071112 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-08-01 16:57:18 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE SIZE OF THE HEADER SUPPORTING THE ROOF HAS BEEN | | CHANGED FROM A NO. SYP DOUBLE 2 X 8 TO A DOUBLE 2 X 6. | | THE HEADER SPAN IS OVER 8 FEET. A 2 X 6 HEADER IS TOO | | SMALL TO HANDLE THE LOADS. PLEASE CORRECT. FBC R301.1 | | | | 2) THE SIMPSON HUS26-2 HANGER REQUIRES (12) 1/4" X | | 2-3/4" TITEN MASONRY SCREWS AND (6) 10D NAILS FOR AN | | UPLIFT OF 1085 LBS ACCORDING TO THE SIMPSON CATALOG. | | PLEASE REVISE. FBC R301.1 | | | | THE REVISION WILL NEED TO BE CORRECTED AND RESUBMITTED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|