Plan Review Notes
Plan Review Notes For Permit 13071064
Permit Number 13071064
Review Stop B
Sequence Number 2
Notes
Date Text
2013-08-13 08:06:55PROVISO;
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) ROOF VENT GAF IR-61 REQUIRES A PRODUCT APPROVAL 2010
 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING & FL S RULE
 9N3, (31)(D) ROOFING PRODUCTS.
  
 2) BEDROOM, ROOM # 102 NEW 6X10 A/C SUPPLY TO BE
 LOCATED BELOW THE 2 HR CEILING, IN THIS LOCATION NO
 FIRE DAMPERS WILL BE REQUIRED.