Plan Review Notes
Plan Review Notes For Permit 13071055
Permit Number 13071055
Review Stop E
Sequence Number 1
Notes
Date Text
2013-08-28 17:45:372010 FBC / 2008 NEC
  
 DENIED BY ELECTRIC
  
 1) PROVIDE LOAD CALCULATIONS AND PANEL SCHEDULE FOR THE
 NEW 100 AMP SUB PANEL.NEC 220.40
  
 2) SHOW THE 100 AMP SUB-PANEL ON THE RISER DIAGRAM (NEC
 215.5). SPECIFY THE WIRING METHOD AND SIZES OF THE
 GROUNDED AND UNGROUNDED CONDUCTORS FEEDING THE 100 AMP
 PANEL (NEC TABLE 310.16) AND THE GROUNDING CONDUCTOR
 SIZE (NEC 250.122).
  
 3) SPECIFY THE RATING OF THE BUS STABS IN THE 150 AMP
 MAIN PANEL NEC 110.3
  