Plan Review Notes For Permit 13071055 |
Permit Number |
13071055 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-08-28 17:45:37 | 2010 FBC / 2008 NEC | | | | DENIED BY ELECTRIC | | | | 1) PROVIDE LOAD CALCULATIONS AND PANEL SCHEDULE FOR THE | | NEW 100 AMP SUB PANEL.NEC 220.40 | | | | 2) SHOW THE 100 AMP SUB-PANEL ON THE RISER DIAGRAM (NEC | | 215.5). SPECIFY THE WIRING METHOD AND SIZES OF THE | | GROUNDED AND UNGROUNDED CONDUCTORS FEEDING THE 100 AMP | | PANEL (NEC TABLE 310.16) AND THE GROUNDING CONDUCTOR | | SIZE (NEC 250.122). | | | | 3) SPECIFY THE RATING OF THE BUS STABS IN THE 150 AMP | | MAIN PANEL NEC 110.3 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|