Plan Review Notes For Permit 13071055 |
Permit Number |
13071055 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-08-16 14:36:00 | RESIDENTIAL (R3) RENOVATION, BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | DCA RULE 9N-3 FOR FLAT ROOF ASSEMBLY. AND, | | A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO | | BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN | | PRESSURES OF SEC. R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL. | | | | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | REQUIRED BY GENERAL LIMITATION # 7. NAIL ENHANCING AT | | PERIMETER AND CORNER AREAS IS ALLOWED BY GENERAL | | LIMITATION #7 (SEE LAST PAGE OF NOA) TO ACHIEVE THE | | DESIGN PRESSURES REQUIRED BY SEC. R301.2.1.4.3. | | | | 2- PROVIDE CURRENT NOA FOR THE ROOF SHINGLES TO BE | | INSTALLED. NOA 11-1122.04 SUBMITTED WAS SUPERSEDED BY | | MIAMI-DADE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 | | |
|