2013-08-16 14:36:00RESIDENTIAL (R3) RENOVATION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR FLAT ROOF ASSEMBLY. AND,
 A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION # 7. NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS IS ALLOWED BY GENERAL
 LIMITATION #7 (SEE LAST PAGE OF NOA) TO ACHIEVE THE
 DESIGN PRESSURES REQUIRED BY SEC. R301.2.1.4.3.
  
 2- PROVIDE CURRENT NOA FOR THE ROOF SHINGLES TO BE
 INSTALLED. NOA 11-1122.04 SUBMITTED WAS SUPERSEDED BY
 MIAMI-DADE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  