2013-08-16 14:49:15 | BUILDING PLAN REVIEW |
| PERMIT: 13071001 |
| ADD: 2119 S DIXIE HWY |
| CONT: TO BE DETERMINED |
| TEL: (561)312-5921 |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: AUGUST 16/2013 |
| ACTION: DENIED |
| |
| INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 1) SHEET SP-2.0 INDICATE AT THE (2) ACCESSIBLE PARKING |
| SPACESFROM THE ACCESS AISLE THERE IS A RAMP TO THE NEW |
| SIDE WALK, PLEASE PROVIDE A DETAIL OF THIS AREA, |
| NORMALLY THERE IS A CURB CUT OR CURB RAMP IN COMPLIANCE |
| WITH 2010 FBC- ACCESSIBILITY CODE 406.1-5. |
| |
| 2) SHEET A1.1: |
| 2A) DISCREPANCIES IN PLANS ON A1.1 FLOOR PLAN, SEE |
| SECTION LABELED DETAIL A/A6 & B/A6 PLEASE REVERSE |
| SECTION DETAIL. |
| DISCREPANCIES IN SECTION TO THE RIGHT OF THE FLOOR PLAN |
| ARE ALSO LABELED WITH THTE SAME A6 SHEET, SHOULD THEY |
| BE LABELED A1? |
| |
| 2B) WAALL LEGEND FOR WALL TYPES INDICATES AND |
| ALTERNATIVE WITH THE WORD "OR". WWEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION, 2010 EDITION, 107.2.1 SUCH DRAWINGS AND |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION. |
| |
| 3) SHEET A6 DETAIL- B INDICATES A SLOPED SCISSOR TYPE |
| TRUSS WITH A SLOPED BOTTOM CORD, SHEET A8 DETAIL A |
| INDICATES THE BOTTOM CHORD OF TRUSSES AT TWO DIFFERNT |
| LEVELS A DISCREPANCY IN DETAILS. PLEASE SEE THE |
| STRUCTURAL S1 ONLY ONE TYPE OF TRUSS IS INDICATED, NOT |
| TWO TYPES OF TRUSSES. |
| |
| 4A) SHEET A8 DETAIL A INDICATES A DROPED CEILING AND |
| THE WALL INSULATION ONLY GOING 6 INCHES ABOVE THE |
| DROPPED CEILING. THIS SHEET ALSO INDICATES THE WALL |
| INSULATION TYPE TO BE R4.1 FOIL INSULATION. PLEASE |
| REFER TO THE ENERGY CALCULATIONS AND THE VALUES |
| PROVIDED THERE SHOW TTHE USE OF .75 INCH ISO INSULATION |
| BETWEEN THE FURRING STRIPS AT 24 INCHES ON CENTER. |
| |
| 4B) THE PLANS DO NOT INDICATE WHERE THE ROOF INSULATION |
| WILL BE PLACED. IF THE ROOF INSULATION A R-19 BRD |
| INSULATION (ENERGY CALCULATIONS) IS PLACED AT THE ROOF |
| LINE, THEN THE END WALL, WALL INSULATION SHOULD |
| CONTINUE TO THE ROOF TOP INSULATION COMPLETING THE |
| ENVELOPE SEAL. |
| |
| 4C) THE RESTROOM FLOOR PLAN INDICATES A 7'-0" WIDE |
| RESTROOM , TO HAVE THE 60 INCH CLEARANCE REQUIRED FOR |
| THE WATER CLOSET REQUIRED FOR THE 2010 FL ACC CODE |
| 604.3.2 THE MINIMUM CLEARANCE WOULD BE 7'-1". SEE 2010 |
| FL ACC CODE FIGURE 604.8.1.6. |
| |
| 5) SHEET S-0: |
| 5A) MISSING SOILS REPORT: 2010 FBC-B 1803.5.2 |
| QUESTIONABLE SOIL. |
| WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY |
| OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE |
| SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE |
| BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| GEOTECHNICAL INVESTIGATION BE CONDUCTED |
| |
| 5B) THE PLANS PROVIDE THE ROOF PRESSURES, PLEASE NOTE |
| IF THE PRESSURES ARE VULT OR VASD. PLEASE NOT ALL |
| PRODUCT APPROVALS ARE EXPRESSED IN VASD. |
| |
| 5C) THE STRUCTURAL SHEETS DO NOT PROVIDE THE PRESSURES |
| FOR WINDOWS & DOORS, 2010 FBC-B 1609.6.4.4.1 COMPONENTS |
| & CLADDING. |
| |
| 5D) NEITHER THE A OR S SHEETS INDICATE THE THICKNESS OF |
| THE ROOF SHEATHING TO BE INSTALLED. |
| |
| 6) SHEET S-1 DETAIL 04/S1 MISSING DETAIL? ADDITIONAL |
| INFORMATION IS REQUIRED. 107.2.1. |
| |
| 7) PRODUCT APPROVALS: |
| 7A) THEMA TRU DOORS, PLEASE PROVIDE COMPLIANCE THAT |
| THESE DOORS WERE TESTED AND LISTED UNDER THE FLORIDA |
| PRODUCT APPROVAL SYSTEM, PROVIDE DOCUMENTATION THEY ARE |
| CURRENT UNDER THE FL 2010 CODE. RULE 9N3 (31)( A). |
| |
| 7B) THE TRULITE STOREFRONT GLAZING SYSTEM CG5000S2 |
| APPEARS TO REFERANCE THE TAS STANDARDS BUT THERE IS NO |
| MIAMI-DADE TEST REPORT SUBMITTED SHOWING A CURRENT NOA, |
| THE PRODUCT APPROVAL REPORT WILL BE REQUIRED BEFORE ANY |
| SHOP DRAWINGS CAN BE REVIEWED FOR CODE COMPLIANCE. RULE |
| 9N3(31)(B). NOTE A MULLION REPORT MAY ALSO BE REQUIRED |
| FOR THE HEIGHTS SHOWN ON SHEET A-7. |
| |
| 7C) PGT PW 701 FIXED WINDOW, PLEASE HIGHLIGHT (CIRCLE) |
| IF THIS IS GOING TO BE A FIN AND FLANGED WINDOW AS WELL |
| AS THE SIZE FOR PRESSURES ON SHEET 2 OF 8. |
| |
| 7D) NOA 11-0329.02 IS EXPIRED, SUBMIT A NEW REPORT, |
| INDICATE THE METHOD OF ANCHORING THE TILE AND MOMENT OF |
| UPLIFT. PLEASE ALSO PROVIDE THE TYPE OF UNDERLAYMENT TO |
| BE INSTALLED. |
| |
| 7E) UNITREX POLYCARBONATE TRANSLUCENT ROOF- PROVIDE |
| PRODUCT TESTING FOR THIS SYSTEM THAT IT MEETS THE 170 |
| MPH 3 SECOND GUST WIND ZONE, 2010 FBC-B 1609.6.4.4.1 |
| COMPONENTS & CLADDING. |
| |
| 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |