Plan Review Notes For Permit 13070997 |
Permit Number |
13070997 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-07-30 13:52:33 | RE-ROOF, BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | LIMITATION #7 ON LAST PAGE OF OF NOA 12-0716.18 | | SUBMITTED. THESE CALCULATIONS ARE REQUIRED TO MEET THE | | DESIGN PRESSURES OF SEC. 1609.4.2 OF 2010 FBC. | | | | 2- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY AND BASE | | SHEET FASTENING OPTION IS GOING TO BE USED TO VERIFY | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. 1609.4.2. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|