2013-11-16 15:19:36 | BUILDING PLAN REVIEW |
| PERMIT: 13070994 |
| ADD: 455 HIBISCUS ST HI-RISE R1-R2 |
| CONT: MOSS & ASSOCIATES |
| TEL: (954)524-5678 |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2ND REVIEW |
| DATE: NOV. 16/ 2013 |
| ACTION:PROVISO |
| |
| 1) SHEET (003) LS1.02 2ND FLOOR: |
| 1A-D) COMPLIED |
| |
| 1E) COMPLIED: R-1 DWELLING UNITS, THE CODE COMMENTARY |
| ALLOWS FOR COOKING UNITS "EXTENDED STAY" FOR NOT MORE |
| THAN 30 DAYS. |
| |
| 1F-J) COMPLIED. |
| |
| 2A-G) COMPLIED. |
| |
| 2H) PROVISO: FIRE COMMAND ROOM AND REQUIRED SYSTEMS. |
| FBC-B 403.4.4 EMERGENCY RESPONDER RADIO COVERAGE. |
| EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN |
| ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE. |
| |
| 2I-J) COMPLIED. PLEASE ALSO INDICATE WHERE COMPLIANCE |
| WITH 403.3.2 WATER SUPPLY TO THE REQUIRED FIRE PUMPS |
| SHALL BE SUPPLIED BY CONNECTIONS TO A MINIMUM OF TWO |
| WATER MAINS LOCATED IN DIFFERENT STREETS. |
| |
| 3A) COMPLIED. |
| |
| 3B) PROVISO: PROVIDE MANUFACURERS CUT SHEETS. PLEASE |
| ALSO PROVIDE CODE COMPLIANCE FOR THE DWELLING UNIT |
| FLOORS FBC-B STRUCTURE BORNE SOUND, TILE FLOORS ETC? |
| 3B)(1) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492 |
| . |
| 3B)(2)FBC-B 2010 603.2 EXCEPTION (1) TILE FLOORING. |
| FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF |
| NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING |
| AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| OF NOT MORE THAN 100. |
| |
| 4-7) COMPLIED. |
| |
| 8) PROVISO: 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 9) PROVISO: |
| BUILDING APPROVED WITH EXCEPTION! |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| |
| MISSING PRODUCT APPROVALS, FLORIDA DEPARTMENT OF |
| COMMUNITY AFFAIRS RULE |
| 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS. OVERHEAD, SWING, AUTO BYPASS, |
| LOUVERED & ROOF HATCHES |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES INCLUDING ROOF TOP |
| CURBS & FANS |
| (E) PRE-ENGINEERED A/C STANDS |
| |
| 10) PRODUCE AN IMPACT FEE RECEIPT THAT IMPACT FEES WERE |
| PAID UNDER THE FOUNDATION PERMIT OR BEFORE A PERMIT TO |
| CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST |
| BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID |
| RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL |
| (561)233-5025 FOR MORE INFORMATION. |
| |