Plan Review Notes
Plan Review Notes For Permit 13070994
Permit Number 13070994
Review Stop B
Sequence Number 2
Notes
Date Text
2013-11-16 15:19:36BUILDING PLAN REVIEW
 PERMIT: 13070994
 ADD: 455 HIBISCUS ST HI-RISE R1-R2
 CONT: MOSS & ASSOCIATES
 TEL: (954)524-5678
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: NOV. 16/ 2013
 ACTION:PROVISO
  
 1) SHEET (003) LS1.02 2ND FLOOR:
 1A-D) COMPLIED
  
 1E) COMPLIED: R-1 DWELLING UNITS, THE CODE COMMENTARY
 ALLOWS FOR COOKING UNITS "EXTENDED STAY" FOR NOT MORE
 THAN 30 DAYS.
  
 1F-J) COMPLIED.
  
 2A-G) COMPLIED.
  
 2H) PROVISO: FIRE COMMAND ROOM AND REQUIRED SYSTEMS.
 FBC-B 403.4.4 EMERGENCY RESPONDER RADIO COVERAGE.
 EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN
 ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE.
  
 2I-J) COMPLIED. PLEASE ALSO INDICATE WHERE COMPLIANCE
 WITH 403.3.2 WATER SUPPLY TO THE REQUIRED FIRE PUMPS
 SHALL BE SUPPLIED BY CONNECTIONS TO A MINIMUM OF TWO
 WATER MAINS LOCATED IN DIFFERENT STREETS.
  
 3A) COMPLIED.
  
 3B) PROVISO: PROVIDE MANUFACURERS CUT SHEETS. PLEASE
 ALSO PROVIDE CODE COMPLIANCE FOR THE DWELLING UNIT
 FLOORS FBC-B STRUCTURE BORNE SOUND, TILE FLOORS ETC?
 3B)(1) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492
 .
 3B)(2)FBC-B 2010 603.2 EXCEPTION (1) TILE FLOORING.
 FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
  
 4-7) COMPLIED.
  
 8) PROVISO: 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) PROVISO:
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 MISSING PRODUCT APPROVALS, FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS. OVERHEAD, SWING, AUTO BYPASS,
 LOUVERED & ROOF HATCHES
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES INCLUDING ROOF TOP
 CURBS & FANS
 (E) PRE-ENGINEERED A/C STANDS
  
 10) PRODUCE AN IMPACT FEE RECEIPT THAT IMPACT FEES WERE
 PAID UNDER THE FOUNDATION PERMIT OR BEFORE A PERMIT TO
 CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST
 BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]