2013-09-04 14:37:25 | FBC 2010 ACCESSIBILITY CODE |
| FBC 2010 PLUMBING REVIEW #1 |
| DENIED: |
| |
| 1. SHEET P1.1 THE MINIMUM HOT WATER SCHEDULE |
| TEMPRATURES SHOWN ARE ABOVE THAT ALLOWED IN THE FLORIDA |
| ENEGRY CODE: |
| 504.3 TEMPERATURE CONTROLS. |
| SERVICE WATER-HEATING EQUIPMENT SHALL BE PROVIDED WITH |
| CONTROLS TO ALLOW A SETPOINT OF 110?F (43?C) FOR |
| EQUIPMENT SERVING DWELLING UNITS AND 90?F (32?C) FOR |
| EQUIPMENT SERVING OTHER OCCUPANCIES. THE OUTLET |
| TEMPERATURE OF LAVATORIES IN PUBLIC FACILITY REST ROOMS |
| SHALL BE LIMITED TO 110?F (43?C). |
| |
| FBC PLUMBING 424.3 INDIVIDUAL SHOWER VALVES: |
| INDIVIDUAL SHOWER AND TUB-SHOWER COMBINATION VALVES |
| SHALL BE BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION |
| BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO |
| THE REQUIREMENTS OF ASSE 1016 OR ASME A112.18.1/CSA |
| B125.1 AND SHALL BE INSTALLED AT THE POINT OF USE. |
| SHOWER AND TUB-SHOWER COMBINATION VALVES REQUIRED BY |
| THIS SECTION SHALL BE EQUIPPED WITH A MEANS TO LIMIT |
| THE MAXIMUM SETTING OF THE VALVE TO 120?F (49?C), WHICH |
| SHALL BE FIELD ADJUSTED IN ACCORDANCE WITH THE |
| MANUFACTURER'S INSTRUCTIONS. IN-LINE THERMOSTATIC |
| VALVES SHALL NOT BE UTILIZED FOR COMPLIANCE WITH THIS |
| SECTION. |
| |
| FOR PUBLIC HAND WASHING: |
| FBC PLUMBING 416.5 TEMPERED WATER FOR PUBLIC |
| HAND-WASHING FACILITIES. |
| TEMPERED WATER SHALL BE DELIVERED FROM PUBLIC |
| HAND-WASHING FACILITIES. TEMPERED WATER SHALL BE |
| DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE |
| LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA |
| B125.3. |
| |
| 2. SHEET P4-1: |
| A. THE RISERS SHOWN APPEAR TO BE WASTE STACK VENTS. |
| WATER CLOSETS ARE NOT PERMITTED ON WASTE STACK VENTS. |
| 910.2 STACK INSTALLATION. |
| THE WASTE STACK SHALL BE VERTICAL, AND BOTH HORIZONTAL |
| AND VERTICAL OFFSETS SHALL BE PROHIBITED BETWEEN THE |
| LOWEST FIXTURE DRAIN CONNECTION AND THE HIGHEST FIXTURE |
| DRAIN CONNECTION. EVERY FIXTURE DRAIN SHALL CONNECT |
| SEPARATELY TO THE WASTE STACK. THE STACK SHALL NOT |
| RECEIVE THE DISCHARGE OF WATER CLOSETS OR URINALS. |
| |
| B. THE VENTS ARE NOT PERMITTED TO BE LESS THAN THE SIZE |
| OF THE WASTE STACK. |
| 910.3 STACK VENT. |
| A STACK VENT SHALL BE PROVIDED FOR THE WASTE STACK. THE |
| SIZE OF THE STACK VENT SHALL BE NOT LESS THAN THE SIZE |
| OF THE WASTE STACK. OFFSETS SHALL BE PERMITTED IN THE |
| STACK VENT, SHALL BE LOCATED AT LEAST 6 INCHES (152 MM) |
| ABOVE THE FLOOD LEVEL OF THE HIGHEST FIXTURE AND SHALL |
| BE IN ACCORDANCE WITH SECTION 905.2. THE STACK VENT |
| SHALL BE PERMITTED TO CONNECT WITH OTHER STACK VENTS |
| AND VENT STACKS IN ACCORDANCE WITH SECTION 903.5. |
| |
| C. THE TWO INCH SINK STACKS ON RISER DETAIL #5 & #7 |
| WOULD BE UNDERSIZED. |
| TABLE 910.4 |
| WASTE STACK VENT SIZE 2" = 4 FIXTURE UNITS |
| |
| D. THE WATER RISER AND DOWNFEED PIPES REQUIRE SEPARATE |
| SHUTOFF VALVES. |
| 606.1 LOCATION OF FULL-OPEN VALVES. |
| FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING |
| LOCATIONS: |
| ON THE BASE OF EVERY WATER RISER PIPE IN OCCUPANCIES |
| OTHER THAN MULTIPLE-FAMILY RESIDENTIAL OCCUPANCIES THAT |
| ARE TWO STORIES OR LESS IN HEIGHT AND IN ONE-AND |
| TWO-FAMILY RESIDENTIAL OCCUPANCIES. |
| ON THE TOP OF EVERY WATER DOWN-FEED PIPE IN OCCUPANCIES |
| OTHER THAN ONE- AND TWO-FAMILY RESIDENTIAL OCCUPANCIES. |
| |
| |
| 3. SHEET P3.2 THE KITCHEN HAND SINKS CONNECTED TO 140 |
| DEGREE HOT WILL REQUIRE MIXING VALVES. |
| 424.7 TEMPERATURE-ACTUATED, FLOW REDUCTION VALVES FOR |
| INDIVIDUAL FIXTURE FITTINGS. |
| TEMPERATURE-ACTUATED, FLOW REDUCTION DEVICES, WHERE |
| INSTALLED FOR INDIVIDUAL FIXTURE FITTINGS, SHALL |
| CONFORM TO ASSE 1062. SUCH VALVES SHALL NOT BE USED |
| ALONE AS A SUBSTITUTE FOR THE BALANCED PRESSURE, |
| THERMOSTATIC OR COMBINATION SHOWER VALVES REQUIRED IN |
| SECTION 424.3. |
| |
| ***PROVISO*** |
| 1. SHEET C-8 THE 12" PVC LINE UNDER THE BUILDING SHALL |
| BE OF A MATERIAL ALLOWED BY FBC PLUMBING TABLE 702.2 |
| SECTION 1102 |
| MATERIALS |
| 1102.1 GENERAL. |
| THE MATERIALS AND METHODS UTILIZED FOR THE CONSTRUCTION |
| AND INSTALLATION OF STORM DRAINAGE SYSTEMS SHALL COMPLY |
| WITH THIS SECTION AND THE APPLICABLE PROVISIONS OF |
| CHAPTER 7. |
| 1102.3 UNDERGROUND BUILDING STORM DRAIN PIPE. |
| UNDERGROUND BUILDING STORM DRAIN PIPE SHALL CONFORM TO |
| ONE OF THE STANDARDS LISTED IN TABLE 702.2. |
| |
| 2. ALL HOSE BIBBS/ WALL HYDRANTS REQUIRE SEPARATE |
| SHUTOFF VALVES. |
| 606.2 LOCATION OF SHUTOFF VALVES. |
| SHUTOFF VALVES SHALL BE INSTALLED IN THE FOLLOWING |
| LOCATIONS: |
| 2. ON THE WATER SUPPLY PIPE TO EACH SILLCOCK IN OTHER |
| THAN ONE- AND TWO-FAMILY RESIDENTIAL OCCUPANCIES. |
| |
| REVIEW BY |
| LARRY WAGNER |
| CHIEF PLUMBING INSPECTOR |
| PHONE # 805-6692 |
| EMAIL [email protected] |
| FAX # 805-6676 |
| |