2013-09-04 14:37:25FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEET P1.1 THE MINIMUM HOT WATER SCHEDULE
 TEMPRATURES SHOWN ARE ABOVE THAT ALLOWED IN THE FLORIDA
 ENEGRY CODE:
 504.3 TEMPERATURE CONTROLS.
 SERVICE WATER-HEATING EQUIPMENT SHALL BE PROVIDED WITH
 CONTROLS TO ALLOW A SETPOINT OF 110?F (43?C) FOR
 EQUIPMENT SERVING DWELLING UNITS AND 90?F (32?C) FOR
 EQUIPMENT SERVING OTHER OCCUPANCIES. THE OUTLET
 TEMPERATURE OF LAVATORIES IN PUBLIC FACILITY REST ROOMS
 SHALL BE LIMITED TO 110?F (43?C).
  
 FBC PLUMBING 424.3 INDIVIDUAL SHOWER VALVES:
 INDIVIDUAL SHOWER AND TUB-SHOWER COMBINATION VALVES
 SHALL BE BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO
 THE REQUIREMENTS OF ASSE 1016 OR ASME A112.18.1/CSA
 B125.1 AND SHALL BE INSTALLED AT THE POINT OF USE.
 SHOWER AND TUB-SHOWER COMBINATION VALVES REQUIRED BY
 THIS SECTION SHALL BE EQUIPPED WITH A MEANS TO LIMIT
 THE MAXIMUM SETTING OF THE VALVE TO 120?F (49?C), WHICH
 SHALL BE FIELD ADJUSTED IN ACCORDANCE WITH THE
 MANUFACTURER'S INSTRUCTIONS. IN-LINE THERMOSTATIC
 VALVES SHALL NOT BE UTILIZED FOR COMPLIANCE WITH THIS
 SECTION.
  
 FOR PUBLIC HAND WASHING:
 FBC PLUMBING 416.5 TEMPERED WATER FOR PUBLIC
 HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM PUBLIC
 HAND-WASHING FACILITIES. TEMPERED WATER SHALL BE
 DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA
 B125.3.
  
 2. SHEET P4-1:
 A. THE RISERS SHOWN APPEAR TO BE WASTE STACK VENTS.
 WATER CLOSETS ARE NOT PERMITTED ON WASTE STACK VENTS.
 910.2 STACK INSTALLATION.
 THE WASTE STACK SHALL BE VERTICAL, AND BOTH HORIZONTAL
 AND VERTICAL OFFSETS SHALL BE PROHIBITED BETWEEN THE
 LOWEST FIXTURE DRAIN CONNECTION AND THE HIGHEST FIXTURE
 DRAIN CONNECTION. EVERY FIXTURE DRAIN SHALL CONNECT
 SEPARATELY TO THE WASTE STACK. THE STACK SHALL NOT
 RECEIVE THE DISCHARGE OF WATER CLOSETS OR URINALS.
  
 B. THE VENTS ARE NOT PERMITTED TO BE LESS THAN THE SIZE
 OF THE WASTE STACK.
 910.3 STACK VENT.
 A STACK VENT SHALL BE PROVIDED FOR THE WASTE STACK. THE
 SIZE OF THE STACK VENT SHALL BE NOT LESS THAN THE SIZE
 OF THE WASTE STACK. OFFSETS SHALL BE PERMITTED IN THE
 STACK VENT, SHALL BE LOCATED AT LEAST 6 INCHES (152 MM)
 ABOVE THE FLOOD LEVEL OF THE HIGHEST FIXTURE AND SHALL
 BE IN ACCORDANCE WITH SECTION 905.2. THE STACK VENT
 SHALL BE PERMITTED TO CONNECT WITH OTHER STACK VENTS
 AND VENT STACKS IN ACCORDANCE WITH SECTION 903.5.
  
 C. THE TWO INCH SINK STACKS ON RISER DETAIL #5 & #7
 WOULD BE UNDERSIZED.
 TABLE 910.4
 WASTE STACK VENT SIZE 2" = 4 FIXTURE UNITS
  
 D. THE WATER RISER AND DOWNFEED PIPES REQUIRE SEPARATE
 SHUTOFF VALVES.
 606.1 LOCATION OF FULL-OPEN VALVES.
 FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 ON THE BASE OF EVERY WATER RISER PIPE IN OCCUPANCIES
 OTHER THAN MULTIPLE-FAMILY RESIDENTIAL OCCUPANCIES THAT
 ARE TWO STORIES OR LESS IN HEIGHT AND IN ONE-AND
 TWO-FAMILY RESIDENTIAL OCCUPANCIES.
 ON THE TOP OF EVERY WATER DOWN-FEED PIPE IN OCCUPANCIES
 OTHER THAN ONE- AND TWO-FAMILY RESIDENTIAL OCCUPANCIES.
  
  
 3. SHEET P3.2 THE KITCHEN HAND SINKS CONNECTED TO 140
 DEGREE HOT WILL REQUIRE MIXING VALVES.
 424.7 TEMPERATURE-ACTUATED, FLOW REDUCTION VALVES FOR
 INDIVIDUAL FIXTURE FITTINGS.
 TEMPERATURE-ACTUATED, FLOW REDUCTION DEVICES, WHERE
 INSTALLED FOR INDIVIDUAL FIXTURE FITTINGS, SHALL
 CONFORM TO ASSE 1062. SUCH VALVES SHALL NOT BE USED
 ALONE AS A SUBSTITUTE FOR THE BALANCED PRESSURE,
 THERMOSTATIC OR COMBINATION SHOWER VALVES REQUIRED IN
 SECTION 424.3.
  
 ***PROVISO***
 1. SHEET C-8 THE 12" PVC LINE UNDER THE BUILDING SHALL
 BE OF A MATERIAL ALLOWED BY FBC PLUMBING TABLE 702.2
 SECTION 1102
 MATERIALS
 1102.1 GENERAL.
 THE MATERIALS AND METHODS UTILIZED FOR THE CONSTRUCTION
 AND INSTALLATION OF STORM DRAINAGE SYSTEMS SHALL COMPLY
 WITH THIS SECTION AND THE APPLICABLE PROVISIONS OF
 CHAPTER 7.
 1102.3 UNDERGROUND BUILDING STORM DRAIN PIPE.
 UNDERGROUND BUILDING STORM DRAIN PIPE SHALL CONFORM TO
 ONE OF THE STANDARDS LISTED IN TABLE 702.2.
  
 2. ALL HOSE BIBBS/ WALL HYDRANTS REQUIRE SEPARATE
 SHUTOFF VALVES.
 606.2 LOCATION OF SHUTOFF VALVES.
 SHUTOFF VALVES SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 2. ON THE WATER SUPPLY PIPE TO EACH SILLCOCK IN OTHER
 THAN ONE- AND TWO-FAMILY RESIDENTIAL OCCUPANCIES.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  