2013-09-14 16:31:25 | REVIEW #: 1ST |
| ACTION: DENIED |
| |
| FBC 2010 CODE FAMILY W/ 2012 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| 1. PAGE M2.1 EXERCISE ROOM 142, TWO OF THE SIX SUPLY |
| REGISTERS DO NOT SHOW THE DUCTS THAT FEED THEM. PLEASE |
| CORRECT. FBC-M 603.1. |
| |
| 2. PAGE M2.1 FIRE PUMP ROOM 141 WALLS CARRY A 2-HOUR |
| FIRE RATING. SHOW HOW DUCT PENETRATION OF THIE REATED |
| WALL IS TO BE PROTECTED PER FBC-M 607.5. |
| |
| 3. PAGE M2.1 TERMINATION ROOM 131 WALLS CARRY A 1-HOUR |
| FIRE RATING. SHOW HOW DUCT PENETRATION OF THIS REATED |
| WALL IS TO BE PROTECTED PER FBC-M 607.5. |
| |
| 4. PAGE M2.1 FIRE ROOM 131 WALLS CARRY A 1-HOUR FIRE |
| RATING. SHOW HOW DUCT PENETRATION OF THIS REATED WALL |
| IS TO BE PROTECTED PER FBC-M 607.5. |
| |
| 5. PAGE M2.1 PREP ROOM 113 COMMERCIAL KITCHEN GREASE |
| EXHAUST SYSTEM REQUIRES SEPARATE PLANS AND PERMIT. |
| |
| 6. PAGE M2.2 THROUGH M2.6: ALL DUCT PENETRATIONS OF |
| RATED SHAFT ENCLOSURES SHALL BE PROTECTED WITH FIRE AND |
| SMOKE DAMPERS PER FBC-M 607.5.5. |
| |
| 7. PAGE M2.2 THROUGH M2.6: PENETRATIONS OF RATED |
| CORRIDOR SHALL BE PROTECTED WITH FIRE AND SMOKE DAMPERS |
| PER FBC-M 607.5.4. |
| |
| 8. PAGE M4.1 PLAN NOTE M18 CALL FOR CONDENSATE TO |
| DISCHARGE INTO SINK P-TRAP. CONDENSATE SHALL NOT |
| DISCHARGE INTO SANITARY SYSTEM PER CITY ORDINANCE. |
| |
| 9. PAGE M4.1 PLAN NOTE M34 CALLS FOR DOOR UNDERCUT FOR |
| RETURN AIR. BALANCED RETURN IS REQUIRED IN ALL |
| HABITABLE ROOMS PER FBC-M 601.4. |
| |
| 10. PROVIDE COOLING AND HEATING LOAD CLACULATIONS. |
| |
| 11. PROVIDE RATIONAL ANALYSIS FOR SMOKE CONTROL SYSTEM |
| PER FBC-B 909.4. |
| |