2013-09-14 16:31:25REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2010 CODE FAMILY W/ 2012 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M2.1 EXERCISE ROOM 142, TWO OF THE SIX SUPLY
 REGISTERS DO NOT SHOW THE DUCTS THAT FEED THEM. PLEASE
 CORRECT. FBC-M 603.1.
  
 2. PAGE M2.1 FIRE PUMP ROOM 141 WALLS CARRY A 2-HOUR
 FIRE RATING. SHOW HOW DUCT PENETRATION OF THIE REATED
 WALL IS TO BE PROTECTED PER FBC-M 607.5.
  
 3. PAGE M2.1 TERMINATION ROOM 131 WALLS CARRY A 1-HOUR
 FIRE RATING. SHOW HOW DUCT PENETRATION OF THIS REATED
 WALL IS TO BE PROTECTED PER FBC-M 607.5.
  
 4. PAGE M2.1 FIRE ROOM 131 WALLS CARRY A 1-HOUR FIRE
 RATING. SHOW HOW DUCT PENETRATION OF THIS REATED WALL
 IS TO BE PROTECTED PER FBC-M 607.5.
  
 5. PAGE M2.1 PREP ROOM 113 COMMERCIAL KITCHEN GREASE
 EXHAUST SYSTEM REQUIRES SEPARATE PLANS AND PERMIT.
  
 6. PAGE M2.2 THROUGH M2.6: ALL DUCT PENETRATIONS OF
 RATED SHAFT ENCLOSURES SHALL BE PROTECTED WITH FIRE AND
 SMOKE DAMPERS PER FBC-M 607.5.5.
  
 7. PAGE M2.2 THROUGH M2.6: PENETRATIONS OF RATED
 CORRIDOR SHALL BE PROTECTED WITH FIRE AND SMOKE DAMPERS
 PER FBC-M 607.5.4.
  
 8. PAGE M4.1 PLAN NOTE M18 CALL FOR CONDENSATE TO
 DISCHARGE INTO SINK P-TRAP. CONDENSATE SHALL NOT
 DISCHARGE INTO SANITARY SYSTEM PER CITY ORDINANCE.
  
 9. PAGE M4.1 PLAN NOTE M34 CALLS FOR DOOR UNDERCUT FOR
 RETURN AIR. BALANCED RETURN IS REQUIRED IN ALL
 HABITABLE ROOMS PER FBC-M 601.4.
  
 10. PROVIDE COOLING AND HEATING LOAD CLACULATIONS.
  
 11. PROVIDE RATIONAL ANALYSIS FOR SMOKE CONTROL SYSTEM
 PER FBC-B 909.4.
  