2013-09-19 14:02:18 | #13070994 |
| 455 HIBISCUS |
| MARRIOTT RESIDENCE INN |
| |
| PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| REVIEW COMMENTS. |
| |
| E1.1 |
| PROVIDE A DESIGNATED CLEAR WORKING SPACE AROUND THE |
| ELECTRICAL SERVICE EQUIPMENT AND PANEL BOARDS. NEC |
| 215.5, 110.26 |
| |
| PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION |
| AND FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. |
| NEC 110.22, 110.16, 110.22 |
| |
| VERIFY THE FIRE PUMP CIRCUIT CONDUCTORS ARE PROPERLY |
| PROTECTED. NEC 695.6 |
| |
| VERIFY THE FIRE PUMP OVER CURRENT PROTECTIVE DEVICES |
| HAVE BEEN SELECTED TO CARRY INDEFINITELY THE SUM OF THE |
| LOCKED-ROTOR CURRENT OF THE FIRE PUMP EQUIPMENT. NEC |
| 694.4 |
| |
| PROVIDE A SIGN AT THE SERVICE-ENTRANCE EQUIPMENT |
| INDICATING TYPE AND LOCATION OF THE ON-SITE EMERGENCY |
| POWER SOURCES. NEC 700.8 |
| |
| PROVIDE SIGNAGE DETAIL FOR ALL FIRE PUMP DISCONNECTS |
| AND CONTROLLERS. NEC 695.4 |
| |
| VERIFY THE POWER SOURCE SUPPLIED BY THE ON-SITE |
| GENERATOR TO THE FIRE PUMP CONNECTS TO A DEDICATED |
| DISCONNECTING MEANS SEPARATE FORM THE OTHER GENERATOR |
| DISCONNECTING MEANS. NEC 695.4 |
| |
| VERIFY THE EMERGENCY CIRCUIT WIRING IS FULLY PROTECTED. |
| NEC 695.14, 700.9 |
| |
| VERIFY THAT ALL WIRING FROM THE EMERGENCY SOURCE HAS |
| BEEN KEPT ENTIRELY INDEPENDENT OF ALL OTHER WIRING AND |
| EQUIPMENT INCLUDING CONTROL CONDUCTORS TO THE |
| GENERATOR. NEC 695.14 700.9(B) |
| |
| PROVIDE LISTING AND SPECIFICATIONS ON THE EMERGENCY |
| ELEVATOR RECALL TRANSFER SWITCH. NEC 110.3 |
| |
| PROVIDE A LOAD SUMMARY FOR THE GENERATOR BRANCH WHICH |
| SUPPORTS ITS SELECTION TO PROVIDE EMERGENCY POWER TO |
| 'EDP', 'E1' AND THE FIRE PUMP. NEC 215.2, 220.40 |
| |
| VERIFY THE GENERATOR HAS DUAL FUEL SUPPLIES. NEC |
| 700.12(B) |
| |
| VERIFY THE EMERGENCY SYSTEM HAS THE CAPACITY TO CONNECT |
| TO A PORTABLE OR TEMPORARY ALTERNATE SOURCE OF POWER |
| WHEN THE GENERATOR IS OUT OF SERVICE FOR MAJOR REPAIR. |
| NEC 700.5 B |
| |
| |
| E1.2 |
| |
| FIRE PUMP FEEDER APPEARS TO BE UNDERSIZED BASED ON THE |
| SELECTED 100 HP FIRE PUMP WITH PRESSURE MAINTENANCE |
| PUMPS. NEC 695.6 |
| |
| VERIFY EQUIPMENT GROUND SELECTION FOR PANEL 'DBP'. NEC |
| T250.122 |
| |
| E1.3 |
| PROVIDE DETAIL FOR FIRE STOPPING OF ALL FLOOR AND WALL |
| PENETRATIONS. NEC 300.21 |
| |
| E1.4 |
| CLARIFY PANEL S2 FED FROM DPX ? WHAT IS DPX? |
| |
| CLARIFY LOCATION OF PANEL C (100 AMP) NOT SHOWN ON |
| MSB-B |
| |
| VERIFY ELEVATOR PIT AND LIGHT FED FROM PANEL 'L' IS NOT |
| CONSIDERED AN EMERGENCY LOAD. |
| |
| VERIFY THE SUMP PUMP FED FROM PANEL 'L' IS NOT |
| CONSIDERED AN EMERGENCY LOAD. |
| |
| E 2.2 |
| VERIFY THE FIRE PUMP HAS BEEN LOCATED WITHIN A ROOM |
| THAT HAS A 2 HOUR RATED FIRE RESISTIVE SEPARATION. FBC |
| 913.2.1 |
| |
| INDICATE THE PROPOSED WIRING METHOD AND CLASSIFICATION |
| FOR THE POOL EQUIPMENT AREA. NEC 505.5 |
| |
| E2.3 |
| VERIFY THE TRANSFORMER VAULT HAS A 3 HOUR FIRE |
| RESISTIVE CONSTRUCTION . NEC 450.42 |
| VERIFY THE ELECTRIC DRINKING FOUNTAIN HAS GFCI |
| PROTECTION. NEC 422.52 |
| |
| E2.5, E2.8, E2.9 |
| |
| LIGHTING TIMERS REQUIRE BACKUP PROTECTION. FBC-EC |
| 505.2.4 |
| |
| VERIFY THE LIGHTING SCENES, SEQUENCING AND CONTROLS |
| MEET THE REQUIREMENTS OF FBC ENERGY CODE. FBC-EC 505.2 |
| |
| PROVIDE LIGHTING POWER DENSITY COMPLIANCE CERTIFICATION |
| ON ELECTRICAL PLANS. FBC-EC 505.503 |
| |
| SEPARATE PERMIT WITH PLANS AND WIND LOAD ENGINEERING |
| FOR POLES WITH LIGHT ASSEMBLY REQUIRED FOR |
| CONSTRUCTION. FBC 1604.1, ASCE 7/10 |
| |
| E3.1 |
| PROVIDE SAFE WORKING CLEARANCE DETAIL/DIMENSIONS ON |
| PLANS FOR ALL GUEST ROOM PANEL BOARDS. NEC 110.26 |
| |
| E5.1 |
| PROVIDE A SUMMARY LOAD CALCULATION FOR THE ELECTRICAL |
| SERVICE, INCLUDING DISTRIBUTION AND GUEST ROOMS. NEC |
| 230.31 |
| |
| |
| NOTE: SEPARATE PERMITS AND PLANS REQUIRED FOR SWIMMING |
| POOL, FIRE ALARM SYSTEM, SITE LIGHTING, LOW VOLTAGE |
| SYSTEMS, ETC. |
| |