Notes |
Date |
Text |
2013-10-16 16:54:05 | THE FOLLOWING SHALL BE ADDRESSED FOR A SUCCESSFUL | | ELECTRICAL PLAN REVIEW: | | 1. MUST SUBMIT A SITE PLAN INDICATING THE AREA TO BE | | WORKED IN. THIS SITE PLAN SHALL INCLUDE THE TOTAL AREA | | OF THE BLDG. TO ASCERTAIN APPLICABLE FBCE REQUIREMENTS. | | APPLICABLE REQUIREMENTS OF THE FBCE SHALL BE INCLUDED | | ON THE SUBMITTED PLANS. | | 2. EXISTING FLOOR PLAN & DEMO PLAN INDICATE THAT THE | | ELECTRICAL PANEL WITHIN UNIT 513 IS BEING RELOCATED, | | THE NEW LOCATION HAS TO BE SHOWN ON THE PLANS. | | 3. AS PER NEC 210.60, THE STORE FRONT/SHOW WINDOW | | OUTLET REQUIREMENTS ARE NOT ADDRESSED ON THE PLANS. | | 4. ELECTRICAL RISER DIAGRAM SHALL INCLUDE PROPER WIRE | | SIZING AND GROUNDING DETAILS. | | | | THIS FILE WAS RETURNED TO THE BIN, PENDING SUBMITTAL OF | | REQUIRED CORRECTIONS BY: MA | | | | |
|