2013-07-29 11:31:53FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1.SHEET 7: BUISNESS OCCUPANCIES WITH OVER 15 OCCUPANTS
 REQUIRE A DRINKING FOUNTAIN. THE ACCESSIBILITY CODE
 REQUIRES THAT IT IS A HI/LOW DRINKING FOUNTAIN.
 FBC PLUMBING 403.1 (D, & E)
 FBC ACCESSIBILITY 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
  
  