2013-07-30 16:12:37511 SOUTH OLIVE AVENUE
 PERMIT #13070893
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE ADDRESS PROVIDED ON THE PLANS (509 S OLIVE AVE)
 DOES NOT MATCH THE ADDRESS (511 S OLIVE AVE) PROVIDED
 ON THE PERMIT APPLICATION.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PROVIDE FIRE EXTINGUISHERS, ILLUMINATION AND
 ILLUMINATED EXIT SIGNS FOR ADJACENT SHELL SPACES.
  
 SHEET 5: IT IS UNCLEAR FROM THE PLAN TO DETERMINE IF
 THE EXISTING DUCT WORK PENETRATES INTO THE ADJACENT
 SHELL SPACE WHEREBY A FIRE DAMPER MAY BE NEEDED.
  
 SHEET 4 & 7: THE EXIT SIGNS AND EMERGENCY LIGHTING WALL
 PACKS SHOWN ON THE LIFE SAFETY PLAN ARE NOT SHOWN ON
 THE ELECTRICAL DRAWING.
  