2013-07-29 14:14:00PROVISO:
 2010 FBC-B 716.4 FIRE DAMPER ACCESS AND IDENTIFICATION.
 2010 FBC-M FIRE DAMPER ACCESS AND IDENTIFICATION.
 FIRE AND SMOKE DAMPERS SHALL BE PROVIDED WITH AN
 APPROVED MEANS OF ACCESS, WHICH IS LARGE ENOUGH TO
 PERMIT INSPECTION AND MAINTENANCE OF THE DAMPER AND ITS
 OPERATING PARTS. THE ACCESS SHALL NOT AFFECT THE
 INTEGRITY OF FIRE-RESISTANCE-RATED ASSEMBLIES. THE
 ACCESS OPENINGS SHALL NOT REDUCE THE FIRE-RESISTANCE
 RATING OF THE ASSEMBLY. ACCESS POINTS SHALL BE
 PERMANENTLY IDENTIFIED ON THE EXTERIOR BY A LABEL
 HAVING LETTERS NOT LESS THAN 1/2 INCH (12.7 MM) IN
 HEIGHT READING: FIRE/SMOKE DAMPER, SMOKE DAMPER OR FIRE
 DAMPER. ACCESS DOORS IN DUCTS SHALL BE TIGHT FITTING
 AND SUITABLE FOR THE REQUIRED DUCT CONSTRUCTION.