Plan Review Notes For Permit 13070783 |
Permit Number |
13070783 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-07-29 16:36:20 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | SEE FBC 2010 RESIDENTIAL 308.5, FBC 2010 BUILDING 2404 | | | | 1. FOR THE BUTT GLASS, PROVIDE A STRUCTURAL PLAN WHICH | | INCLUDES THE FOLLOWING INFORMATION: | | | | METAL CHANNEL SPECIFICATION | | FASTENING TO SUBSTRATE | | ASSEMBLY DESIGN PRESSURE LIMITATION | | DESIGN PRESSURES FOR THE STRUCTURE | | SEALANTS (MANUFACTURER AND PRODUCT, SPEC SHEETS) AND | | SPECIFICATION (THICKNESS) | | SIZE OF GLASS | | GLASS SPECIFICATION | | | | IF PLANS ARE NOT PREPARED, SIGNED AND SEALED BY A | | DESIGN PROFESSIONAL, CALCULATIONS MAY BE REQUIRED. | | |
|