Plan Review Notes
Plan Review Notes For Permit 13070764
Permit Number 13070764
Review Stop E
Sequence Number 1
Notes
Date Text
2013-07-30 16:19:17BASED ON ADDITIONAL RECEIVED FROM CONTRACTOR REGARDING
 THE RATED CEILING EXISTING ABOVE THE NEW DROP CEILING,
 PLAN IS BEING APPROVED WITH NOTES REGARDING PROTECTION
 OF ANY PENETRATION OF RATED CEILING. PLACED BACK IN
 DENIED UNDER "C" DUE TO MECHANICAL NOT SIGNING OFF. DH
 7/30/13
2013-07-26 10:05:12PUT IN DENIED UNDER "C" DH
  
 PROVIDE DETAILS OF RATED PENETRATIONS, INCLUDING
 CEILING BOXES AND OTHER ITEMS, 300.22. PROVIDE DETAILS
 OF CEILING FIXTURE SUPPORT AND ATTACHMENT SHOWING FIRE
 RATING DESIGN NUMBER. 410.36