2013-10-09 15:44:17PERMIT # 13070752
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ***REPEAT COMMENTS***
 ***PROVISO***
  
 TO MINIMIZE NUISANCE ALARMS FOR THE BUILDING, THE SMOKE
 ALARMS AND/OR CARBON MONOXIDE DETECTORS WITHIN THE
 INDIVIDUAL RESIDENTIAL SPACES SHALL NOT BE TIED INTO
 THE BUILDINGS FIRE ALARM SYSTEM, PER SECTION 9.6.2.10.4
 OF NFPA 101.
  
 PER NFPA 72 SECTION 7.4.41, SLEEPING AREA NOTIFICATION
 APPLICANCES SHALL HAVE A SOUND LEVEL OF AT LEAST 15 DB
 ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5 DB ABOVE THE
 MAXIMUM SOUND LEVEL HAVING A DURATION OF AT LEAST 60
 SECONDS OR A SOUND LEVEL OF AT LEAST 75 DBA, WHICHEVER
 IS GREATER, MEASURED AT THE PILLOW LEVEL IN THE AREA
 REQUIRED TO BE SERVED BY THE SYSTEM USING THE
 A-WEIGHTED SCALE (DBA).
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  