Plan Review Notes For Permit 13070752 |
Permit Number |
13070752 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-10-23 19:33:56 | THE ELECTRICAL PLAN REVIEW SHOWED NONCOMPLIANCE WITH | | THE REQUIREMENTS OF NEC 210.52 (A)(1) THROUGH (A)(3). | | FILE COPY OF THE PLANS HAVE BEEN MARKED ACCORDINGLY. | | THERE SHALL BE A FLOOR OUTLET ON THE FLOOR LINE ALONG | | THE RAIL AS WELL AS ON THE AREAS OF THE POT SHELVING, | | AND ANY OTHER AREA FOUND TO BE MISSING SUCH BY THE | | FIELD INSPECTOR. | | AS PER NEC 210. 12(B) ACFI IS REQUIRED THROUGH OUT. | | AS PER NEC 406.11 TAMPER-RESISTANT RECEPTACLE ARE | | REQUIRED | | AS PER FBC 314 & 315 SMOKE DETECTORS SHALL BE REQUIRED |
|