2013-10-23 19:33:56THE ELECTRICAL PLAN REVIEW SHOWED NONCOMPLIANCE WITH
 THE REQUIREMENTS OF NEC 210.52 (A)(1) THROUGH (A)(3).
 FILE COPY OF THE PLANS HAVE BEEN MARKED ACCORDINGLY.
 THERE SHALL BE A FLOOR OUTLET ON THE FLOOR LINE ALONG
 THE RAIL AS WELL AS ON THE AREAS OF THE POT SHELVING,
 AND ANY OTHER AREA FOUND TO BE MISSING SUCH BY THE
 FIELD INSPECTOR.
 AS PER NEC 210. 12(B) ACFI IS REQUIRED THROUGH OUT.
 AS PER NEC 406.11 TAMPER-RESISTANT RECEPTACLE ARE
 REQUIRED
 AS PER FBC 314 & 315 SMOKE DETECTORS SHALL BE REQUIRED