Plan Review Notes
Plan Review Notes For Permit 13070748
Permit Number 13070748
Review Stop M
Sequence Number 1
Notes
Date Text
2013-08-14 10:24:27PASS PROVISO
 1) REFER TO SECTION 304.1 GENERAL. PROVIDE
 MANUFACTURER'S INSTALLATION
 INSTRUCTIONS ON THE DRYER AND AIR CONDITIONING
 EQUIPMENT.
 2010 FBC (M) AT FIRST INSPECTION.
 2) REFER TO SECTION 602.2.1 MATERIALS WITH IN PLENUM'S.
 ( DON'T INSTALL WOOD DOORS ON A/C CLOSET )
 2010 FBC (M)
 3) REFER TO SECTION 713.3.1.1 FIRE RESISTANCE RATED
 ASSEMBLIES
 2010 FBC. ( PROVIDE A LISTED DETAIL FROM THE ENGINEER
 ON HOW THE
 REFRIGERANT LINES LEAVE THE SHAFT.AT FIRST INSPECTION.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  