2013-07-24 13:38:49 | BUILDING PLAN REVIEW |
| PERMIT: 13070645 |
| ADD: 310 OKEECHOBEE BLVD |
| CONT: BOBLING ARCHITECTURE |
| TEL: (561)662-0000 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: JULY 24/ 2013 |
| ACTION: DENIED |
| |
| 1) SHEET A1 THE NEW DOOR # 002APPEARS TO BE IN A |
| VERTICAL EXIT. IF THIS IS A REQUIRED EXIT AND NOT A |
| CONVENIENCE STAIR THEN THE 2010 FBC-B SECTION 1022.4 |
| APPLIES. 022.4 PENETRATIONS. PENETRATIONS INTO AND |
| OPENINGS THROUGH AN EXIT ENCLOSURE ARE PROHIBITED |
| EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK |
| NECESSARY FOR INDEPENDENT VENTILATION OR |
| PRESSURIZATION, SPRINKLER PIPING, STANDPIPES, |
| ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION |
| SYSTEMS AND ELECTRICAL RACEWAY SERVING THE EXIT |
| ENCLOSURE AND TERMINATING AT A STEEL BOX NOT EXCEEDING |
| 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE |
| PROTECTED IN ACCORDANCE WITH SECTION 713. THERE SHALL |
| BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER |
| PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES. |
| JAMES A. WITMER CBO |