2013-07-24 15:29:57 | FBC 2010 EXISTING BUILDING CODE |
| FBC 2010 ACCESSIBILITY CODE |
| FBC 2010 PLUMBING REVIEW #1 |
| DENIED: |
| |
| 1. THE TOILET COMPARTMENTS ARE REQUIRED TO CONTAIN A |
| LAVATORY. THE LAVITORY SHALL NOT BE IN THE REQUIRED |
| CLEAR SPACE FOR THE WATER CLOSET. |
| 604.8.1.1 SIZE. |
| WHEELCHAIR ACCESSIBLE COMPARTMENTS SHALL BE 60 INCHES |
| (1525 MM) WIDE MINIMUM MEASURED PERPENDICULAR TO THE |
| SIDE WALL, AND 56 INCHES (1420 MM) DEEP MINIMUM FOR |
| WALL HUNG WATER CLOSETS AND 59 INCHES (1500 MM) DEEP |
| MINIMUM FOR FLOOR MOUNTED WATER CLOSETS MEASURED |
| PERPENDICULAR TO THE REAR WALL. |
| FBC ACCESSIBILITY 2010 604.8.1.6 LAVATORY. |
| IN NEW CONSTRUCTION, THE WHEELCHAIR ACCESSIBLE TOILET |
| COMPARTMENT SHALL CONTAIN AN ACCESSIBLE LAVATORY WITHIN |
| IT, WHICH MUST BE AT LEAST 19 INCHES WIDE BY 17 INCHES |
| DEEP, NOMINAL SIZE, AND WALL-MOUNTED. THE LAVATORY |
| SHALL BE MOUNTED SO AS NOT TO OVERLAP THE CLEAR FLOOR |
| SPACE AREAS REQUIRED BY SECTION 604 FOR THE WHEELCHAIR |
| ACCESSIBLE TOILET COMPARTMENT AND SHALL COMPLY WITH |
| SECTION 606. SUCH LAVATORIES SHALL BE COUNTED AS PART |
| OF THE REQUIRED FIXTURE COUNT FOR THE BUILDING. SEE |
| ALSO SECTION 213.3.4. |
| |
| 2. A HI/LOW DRINKING FOUNTAIN WILL BE REQUIRED. |
| FBC PLUMBING TABLE 403.1 |
| FBC ACCESSIBILITY 211.2 MINIMUM NUMBER. |
| NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| 602.7. |
| |
| |