2013-07-31 17:33:59 | PLEASE REVISE PLANS AND/OR RESPOND TO THE FOLLOWING | | COMMENTS. | | ALL CONSTRUCTION POWER TO BE GFCI PROTECTED 590.6 | | LIGHTING AND POWER TO BE ON SEPARATE CIRCUITS FOR | | CONSTRUCTION | | PROVIDE DETAILS OF FIRE RATED PENETRATIONS, NOT A NOTE | | ON THE PLAN TO PROPERLY INSTALL | | SEPARATE PERMITS REQUIRED FOR AUDIO, VISUAL, DATA, POS, | | ALARM, PHONE, OTHER LOW VOLTAGE | | |
|