Plan Review Notes For Permit 13070545 |
Permit Number |
13070545 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-10-22 17:03:47 | SENT TO SH DESK | 2013-10-22 17:03:00 | THE ELECTRICAL RISER DIAGRAM IS NOT CONSISTENT WITH THE | | FLOOR PLAN. REVISE EITHER THE RISER DIAGRAM TO INDICATE | | THE ITEMS BEING INSTALLED NOW, OR SHOW THE REMAINDER OF | | THE ELECTRICAL APPARATUS ON THE FLOOR PLANS. | | INDICATE ON THE SITE PLAN WHERE THE ELECTRICAL SERVICE | | IS DRAWN FROM. | | |
|