Plan Review Notes For Permit 13070545 |
Permit Number |
13070545 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-08-15 16:20:53 | NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW | | COMMENTS. | | CODE: 2010 FBC. | | | | 1- THERE IS NO RETURN AIR FOR BEDROOM #3. SEC. M1602 OF | | 2010 FBC-RESIDENTIAL. | | | | 2- THERE ARE TWO AHU #2 SHOWN ON PLANS. ONE ON THE | | FIRST FLOOR AND ANOTHER ONE ON THE SECOND FLOOR. REVISE | | AS REQUIRED. AND, THERE ARE TWO BEDROOMS #4. REVISE AS | | REQUIRED. SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | | | 3- GUEST STUDIO UNIT #4. RETURN AIR CAN'T BE TAKEN FROM | | THE KITCHEN. REVISE AS REQUIRED. SEC. M1602.2 | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|