2013-08-15 16:20:53NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- THERE IS NO RETURN AIR FOR BEDROOM #3. SEC. M1602 OF
 2010 FBC-RESIDENTIAL.
  
 2- THERE ARE TWO AHU #2 SHOWN ON PLANS. ONE ON THE
 FIRST FLOOR AND ANOTHER ONE ON THE SECOND FLOOR. REVISE
 AS REQUIRED. AND, THERE ARE TWO BEDROOMS #4. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 3- GUEST STUDIO UNIT #4. RETURN AIR CAN'T BE TAKEN FROM
 THE KITCHEN. REVISE AS REQUIRED. SEC. M1602.2
  