2013-08-09 12:26:38NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- BRING PLANS TO PALM BEACH COUNTY TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK COUNTY STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- PROVIDE DRAINAGE PLAN. SEC. R401.3 OF 2010
 FBC-RESIDENTIAL.
  
 3- NEED AT LEAST ONE BATHROOM LOCATED WITH MAXIMUM
 POSSIBLY PRIVACY AND A DOOR THAT HAS 29" CLEAR OPENING.
 THE BATHROOM FOR THE GUEST ROOM IS THE ONE WITH MORE
 PRIVACY, BUT THE DOOR NEEDS TO BE REVISED. SEC. R320.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ALL DIFFERENT SHUTTERS AS SPECIFIED ON PLANS. AND,
 PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE.
  
 B) CEMENTITIOUS SIDING AS SPECIFIED ON PLANS.
  
 C) CONCRETE ROOF TILE. NOA 09-0422.11 SUBMITTED EXPIRED
 ON 12/16/12.
  
 D) ROOF TILE ADHESIVE AS LISTED ON ROOF TILE NOA, IF
 SPECIFIED BY THE DESIGNER OF RECORD. SEE ITEM #22
 BELOW.
  
 E) BALCONIES WATERPROOFING THAT IS DESIGNED TO RECEIVE
 FINISHES AS SPECIFIED BY THE ARCHITECT. (NOTE; CHECK
 DESIGN PRESSURES ON SELECTED ASSEMBLY. RAS 117
 CALCULATIONS MAY BE REQUIRED. SEE GENERAL LIMITATION #7
 ON NOA SUBMITTED).
  
 F) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 G) ALL SIMPSON OR USP STRUCTURAL CONNECTORS SPECIFIED
 ON PLANS, DETAILS AND SECTIONS. NOTE: PROVIDE ONLY THE
 PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE
 SPECIFIED CONNECTOR.
  
 H) BORAL TILESEAL UNDERLAYMENT FOR ROOF TILE. NOA
 12-0417.06 SUBMITTED WAS SUPERSEDED BY MIAMI-DADE. NEED
 TO SUBMIT CURRENT NOA.
  
 I) GARAGE DOOR. NOA 09-0929.10 SUBMITTED WAS SUPERSEDED
 BY MIAMI-DADE. NEED TO SUBMIT CURRENT NOA.
  
 J) INSWING ENTRY DOOR AS SHOWN ON PLANS FOR GUEST
 STUDIO.
  
 K) ENTRY DOOR WITH SIDELITES THAT MEETS THE REVISED
 DESIGN PRESSURES AS REQUIRED BY ITEM #15A BELOW.
  
 L) CASEMENT WINDOWS. NOA 11-1110.18 SUBMITTED EXPIRED
 ON MAY 22, 2013.
 ***NOTE: CLEARLY MARK SPECIFIC WINDOW SIZE AND GLASS
 TYPE TO VERIFY COMPLIANCE WITH THE REVISED DESIGN
 PRESSURES.
  
 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING & SEALING) ALL THE PRODUCT APPROVALS. SEC.
 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 6- SPECIFY ON MULLION PRODUCT APPROVAL WHICH MULLION
 SIZES ARE GOING TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES REQUIRED BY SEC.
 R301.2.1.4.3.
  
 7- PROVIDE COMPLETE ENGINEERING PACKAGE FOR THE
 INSTALLATION OF THE SCREEN ENCLOSURE IN REAR LOGGIA.
 SEC. 107.2.1.3 CITY AMENDMENTS.
  
 8- PROVIDE COMPLETE ENGINEERED PACKAGE FOR THE
 CONSTRUCTION OF THE "ZEN PERGOLA" AS SPECIFIED ON SHEET
 S3.01. SEC. 107.2.1.3 OF CITY AMENDMENTS.
  
 9- PROVIDE COMPLETE SPECIFICATIONS FOR THE
 DWELLING/GARAGE FIRE SEPARATION AS REQUIRED BY SEC.
 R302.6.
  
 10 - SPECIFY ATTIC ACCESS: A)IN GUEST ROOM WING.
 B)LIVING AREA. SEC. R807.
  
 11- DRAWINGS SUBMITTED ARE TOO LIGHT FOR SCANNING FOR
 OUR RECORDS. PLEASE SUBMIT DARKER DRAWINGS TO
 FACILITATE THE SCANNING AND RECORDS RETENTION PROCESS.
 SEC. 107.2.1.4 OF CITY AMENDMENTS.
  
 12- A) WINDOW SCHEDULE ON SHEET A.15: CLARIFY NUMBER OF
 WINDOWS AND SIZE FOR EGRESS WINDOW "C" FOR BEDROOM #3
 AND STUDIO BEDROOM. SEC. R310.
 INFORMATION SHOWN ON THE WINDOW SCHEDULE DON'T MATCH
 ELEVATIONS. REVISE AS REQUIRED.
  
 B) PROVIDE MANUFACTURER CUT SHEETS SHOWING CLEAR
 OPENING DIMENSIONS FOR THE EGRESS WINDOWS TO VERIFY
 COMPLIANCE WITH SEC. R310.
  
  
 13- PROVIDE SOIL TEST REPORT. SEC. R401.4.
  
 14- SHEET S1.00:
 A) ACCORDING TO SEC. R301.2.1.4.3 THIS BUILDING IS
 LOCATED IN EXPOSURE "D" NOT "C". REVISE THE EXPOSURE
 AND THE DESIGN PRESSURES FOR COMPONENTS AND CLADDING.
  
 B) SPECIFY ALL DEAD LOADS, LIVE LOADS , INCLUDING THE
 ATTIC LIVE LOAD AS REQUIRED BY SEC. R301.1 AND TABLE
 R301.5.
  
 C) FOUNDATION NOTE #1 SPECIFIES A SOIL BEARING CAPACITY
 OF 2000PSF. PROVIDE CALCULATIONS SHOWING THAT THIS
 BEARING CAPACITY IS ADEQUATE FOR THE PROPOSED TWO STORY
 MASONRY CONSTRUCTION AND CONCRETE ROOF TILE. SEC.
 107.2.1.3 OF CITY AMENDMENTS.
  
 D) REVISE FASTENER SUBSTITUTION NOTES. ONLY 8D RING
 SHANK NAILS ARE ALLOWED. NOT 8D COMMON NAIL. SEC.
 R803.2.3.1.
  
 E) REVISE DIMENSION FOR GABLE END ROOF ZONE #3. NEED TO
 SPECIFY 5'-0" MIN. SEE FIGURE R803.2.3.1.
  
 15- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE STAIRWAYS (SEC. R311.7), HANDRAILS (SEC.
 R311.7.7) AND GUARDRAILS (SEC. R312 AND TABLE) AND
 TABLE R301.5.
  
 16- PROVIDE COMPLETE WALL SECTIONS, SPECIFICATIONS AND
 FRAMING DETAILS FOR THE TWO FIREPLACES AS SHOWN ON
 PLANS TO SHOW COMPLIANCE WITH SEC. R301.1, R1001, R1004
 AND R1005.
  
 17- PROVIDE MANUFACTURER SPECIFICATIONS FOR THE
 "ICYNENE" INSULATION SPECIFIED ON PLANS. SEC. 103.1 OF
 2010 FBC-ENERGY CONSERVATION.
  
 18- PROVIDE STRUCTURAL BUCK DETAIL FOR GARAGE DOOR, ALL
 SWING AND SLIDING GLASS DOORS AND ALL WINDOWS,
 INCLUDING THE OVAL WINDOW. SEC. R612.10.2.1.
  
 19- PROVIDE SPECIFICATIONS SHOWING HOW GETTING THE
 R-VALUE ON WALLS AS SPECIFIED ON THE ENERGY
 CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION. AND, COORDINATE ALL INFORMATION ON PLANS
 WITH INFORMATION GIVEN ON THE ENERGY CALCULATIONS.
 INCLUDING WINDOWS AND DOORS MATERIAL TYPE, EX: WOOD OR
 METAL. TINTED OR CLEAR, ETC.
  
 20- REVISE ENERGY CALCULATIONS AND COORDINATE WITH
 PLANS SUBMITTED (SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION) AND, COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER NAME:
 A) ITEM #8B: CLARIFY FLOOR OVER OTHER SPACE HAS AN
 R-VALUE OF 0. SEE TABLE 402.4.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 B) ITEM #8C: CLARIFY WHAT IS THE OTHER FLOOR TYPE. AND
 WHY R-VALUE IS 0. SEE TABLE 402.4.2 OF 2010-FBC-ENERGY
 CONSERVATION.
  
 C) REVISE ROOF TYPE TO MATCH PLANS.
  
 D) CLARIFY WHY WINDOW FRAME IS "NONE".
  
 21- DESIGNER OF RECORD TO SPECIFY HOW IS THE ROOF
 CONCRETE ROOF TILE GOING TO BE INSTALLED AS REQUIRED BY
 SEC. 107.2.1.2 OF CITY AMENDMENTS. SPECIFY THE UPLIFT
 LOADS FOR ALL ROOF ZONES. REMEMBER THAT THIS PROPERTY
 IS LOCATED ON FLOOD ZONE "D".
  
 ***REMAINDER: PROPERTY IS LOCATE ON FLOOD ZONE A5.
 ELEVATION CERTIFICATES ARE REQUIRED.
  
 *** PLEASE SUBMIT REPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  