2013-08-25 09:54:19 | BUILDING PLAN REVIEW |
| PERMIT: 13070531 |
| ADD: 6751 N JOG RD |
| CONT: HEDRICK BROTHERS |
| TEL: (561)###-#### |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: SUNDAY/ AUGUST 25/ 2013 |
| ACTION: BUILDING APPROVED WITH EXCEPTION! |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| |
| TYPE BUILDING: II-B |
| SPRINKLERED |
| |
| 1) (20) SHEET 710-A2-100 FINISH SCHEDULE |
| SEE: |
| CORRIDOR C-200- CARPET TILE |
| CONFERENCE RM C-201-CARPET TILE |
| EAST STAIR- RUBBER TILE |
| PLEASE SHOW COMPLIANCE WITH: |
| 2010 FBC-B TABLW 803.9 FLOOR FINISHES FOR OCCUPANCY |
| TYPE A3/ SPRINKLERED BUILDING |
| EXIT ENCLOSURES- B |
| CORRIDORS- B |
| ENCLOSED SPACES- C |
| |
| ALSO SECTION 804.4.1 MINIMUM CRITICAL RADIANT FLUX. |
| INTERIOR FLOOR FINISH AND FLOOR COVERING MATERIALS IN |
| EXIT ENCLOSURES, EXIT PASSAGEWAYS AND CORRIDORS SHALL |
| NOT BE LESS THAN CLASS I IN GROUPS I-1, I-2 AND I-3 AND |
| NOT LESS THAN CLASS II IN GROUPS A, B, E, H, M, R-1, |
| R-2 AND S. IN ALL AREAS, FLOOR COVERING MATERIALS SHALL |
| COMPLY WITH THE DOCFF-1 ?PILL TEST? (CPSC 16 CFR, PART |
| 1630). |
| |
| 2) (23)710-A3-102 ELEVATIONS INDICATE THE USE OF 2 INCH |
| MOUNTED WIRE MESH IN-FILL MOUNTED IN STEEL FRAME |
| CHANNEL FRAME, THE ARCHITECTURAL NOR STRUCTURAL SHEETS |
| SHOW COMPLIANCE WITH 2010 FBC-B 1607.7.1.2 COMPONENTS. |
| INTERMEDIATE RAILS (ALL THOSE EXCEPT THE HANDRAIL), |
| BALUSTERS AND PANEL FILLERS SHALL BE DESIGNED TO |
| WITHSTAND A HORIZONTALLY APPLIED NORMAL LOAD OF 50 |
| POUNDS (0.22 KN) ON AN AREA EQUAL TO 1 SQUARE FOOT |
| (0.0929 M2), INCLUDING OPENINGS AND SPACE BETWEEN |
| RAILS. REACTIONS DUE TO THIS LOADING ARE NOT REQUIRED |
| TO BE SUPERIMPOSED WITH THOSE OF SECTION 1607.7.1 OR |
| 1607.7.1.1. |
| |
| 3) (28) 710-A3-107 SECTION # 1 EAST STAIR INDICATES A |
| SUSPENDED ACCENT CANOPY IN THE STAIRWELL, PLEASE SHOW |
| COMPLIANCE WITH; |
| 2010 FBC-B TABLE 803.9 CEILINGS |
| EXIT ENCLOSURE, A3/ SPRINKLERED TYPE "A" FINISHES. |
| |
| ALSO COMPLIANCE WITH SECTION: 2010 FBC-B 806.1 GENERAL |
| REQUIREMENTS. |
| IN OCCUPANCIES IN GROUPS A, E, I AND R-1 AND |
| DORMITORIES IN GROUP R-2, CURTAINS, DRAPERIES, HANGINGS |
| AND OTHER DECORATIVE MATERIALS SUSPENDED FROM WALLS OR |
| CEILINGS SHALL MEET THE FLAME PROPAGATION PERFORMANCE |
| CRITERIA OF NFPA 701 IN ACCORDANCE WITH SECTION 806.2 |
| OR BE NONCOMBUSTIBLE. |
| |
| 4) (74) 710-S3-202 SECTION # 1 ALUMINUM GAURDRAIL |
| SYSTEM, AND MOUNTING PLATE, PLANS DO NOT SHOW |
| COMPLIANCE WITH : 2010 FBC-B 1607.7.1.1 CONCENTRATED |
| LOAD. |
| HANDRAILS AND GUARDS SHALL BE ABLE TO RESIST A SINGLE |
| CONCENTRATED LOAD OF 200 POUNDS (0.89 KN), APPLIED IN |
| ANY DIRECTION AT ANY POINT ALONG THE TOP, AND TO |
| TRANSFER THIS LOAD THROUGH THE SUPPORTS TO THE |
| STRUCTURE. THIS LOAD NEED NOT BE ASSUMED TO ACT |
| CONCURRENTLY WITH THE LOADS SPECIFIED IN SECTION |
| 1607.7.1. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |
| |
| |
| |
| PLEASE PROVIDE COMPLIANCE WITH |
| |
| EXCEPTION: WHERE A BUILDING IS EQUIPPED THROUGHOUT WITH |
| AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| SECTION 903.3.1.1 OR 903.3.1.2, CLASS II MATERIALS ARE |
| PERMITTED IN ANY AREA WHERE CLASS I MATERIALS ARE |
| REQUIRED, AND MATERIALS COMPLYING WITH THE DOC FF-1 |
| ?PILL TEST? (CPSC 16 CFR, PART 1630) ARE PERMITTED IN |
| ANY AREA WHERE CLASS II MATERIALS ARE REQUIRED. |
| |
| |
| |