Plan Review Notes
Plan Review Notes For Permit 13070531
Permit Number 13070531
Review Stop B
Sequence Number 1
Notes
Date Text
2013-08-25 09:54:19BUILDING PLAN REVIEW
 PERMIT: 13070531
 ADD: 6751 N JOG RD
 CONT: HEDRICK BROTHERS
 TEL: (561)###-####
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUNDAY/ AUGUST 25/ 2013
 ACTION: BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 TYPE BUILDING: II-B
 SPRINKLERED
  
 1) (20) SHEET 710-A2-100 FINISH SCHEDULE
 SEE:
 CORRIDOR C-200- CARPET TILE
 CONFERENCE RM C-201-CARPET TILE
 EAST STAIR- RUBBER TILE
 PLEASE SHOW COMPLIANCE WITH:
 2010 FBC-B TABLW 803.9 FLOOR FINISHES FOR OCCUPANCY
 TYPE A3/ SPRINKLERED BUILDING
 EXIT ENCLOSURES- B
 CORRIDORS- B
 ENCLOSED SPACES- C
  
 ALSO SECTION 804.4.1 MINIMUM CRITICAL RADIANT FLUX.
 INTERIOR FLOOR FINISH AND FLOOR COVERING MATERIALS IN
 EXIT ENCLOSURES, EXIT PASSAGEWAYS AND CORRIDORS SHALL
 NOT BE LESS THAN CLASS I IN GROUPS I-1, I-2 AND I-3 AND
 NOT LESS THAN CLASS II IN GROUPS A, B, E, H, M, R-1,
 R-2 AND S. IN ALL AREAS, FLOOR COVERING MATERIALS SHALL
 COMPLY WITH THE DOCFF-1 ?PILL TEST? (CPSC 16 CFR, PART
 1630).
  
 2) (23)710-A3-102 ELEVATIONS INDICATE THE USE OF 2 INCH
 MOUNTED WIRE MESH IN-FILL MOUNTED IN STEEL FRAME
 CHANNEL FRAME, THE ARCHITECTURAL NOR STRUCTURAL SHEETS
 SHOW COMPLIANCE WITH 2010 FBC-B 1607.7.1.2 COMPONENTS.
 INTERMEDIATE RAILS (ALL THOSE EXCEPT THE HANDRAIL),
 BALUSTERS AND PANEL FILLERS SHALL BE DESIGNED TO
 WITHSTAND A HORIZONTALLY APPLIED NORMAL LOAD OF 50
 POUNDS (0.22 KN) ON AN AREA EQUAL TO 1 SQUARE FOOT
 (0.0929 M2), INCLUDING OPENINGS AND SPACE BETWEEN
 RAILS. REACTIONS DUE TO THIS LOADING ARE NOT REQUIRED
 TO BE SUPERIMPOSED WITH THOSE OF SECTION 1607.7.1 OR
 1607.7.1.1.
  
 3) (28) 710-A3-107 SECTION # 1 EAST STAIR INDICATES A
 SUSPENDED ACCENT CANOPY IN THE STAIRWELL, PLEASE SHOW
 COMPLIANCE WITH;
 2010 FBC-B TABLE 803.9 CEILINGS
 EXIT ENCLOSURE, A3/ SPRINKLERED TYPE "A" FINISHES.
  
 ALSO COMPLIANCE WITH SECTION: 2010 FBC-B 806.1 GENERAL
 REQUIREMENTS.
 IN OCCUPANCIES IN GROUPS A, E, I AND R-1 AND
 DORMITORIES IN GROUP R-2, CURTAINS, DRAPERIES, HANGINGS
 AND OTHER DECORATIVE MATERIALS SUSPENDED FROM WALLS OR
 CEILINGS SHALL MEET THE FLAME PROPAGATION PERFORMANCE
 CRITERIA OF NFPA 701 IN ACCORDANCE WITH SECTION 806.2
 OR BE NONCOMBUSTIBLE.
  
 4) (74) 710-S3-202 SECTION # 1 ALUMINUM GAURDRAIL
 SYSTEM, AND MOUNTING PLATE, PLANS DO NOT SHOW
 COMPLIANCE WITH : 2010 FBC-B 1607.7.1.1 CONCENTRATED
 LOAD.
 HANDRAILS AND GUARDS SHALL BE ABLE TO RESIST A SINGLE
 CONCENTRATED LOAD OF 200 POUNDS (0.89 KN), APPLIED IN
 ANY DIRECTION AT ANY POINT ALONG THE TOP, AND TO
 TRANSFER THIS LOAD THROUGH THE SUPPORTS TO THE
 STRUCTURE. THIS LOAD NEED NOT BE ASSUMED TO ACT
 CONCURRENTLY WITH THE LOADS SPECIFIED IN SECTION
 1607.7.1.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
 PLEASE PROVIDE COMPLIANCE WITH
  
 EXCEPTION: WHERE A BUILDING IS EQUIPPED THROUGHOUT WITH
 AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 903.3.1.1 OR 903.3.1.2, CLASS II MATERIALS ARE
 PERMITTED IN ANY AREA WHERE CLASS I MATERIALS ARE
 REQUIRED, AND MATERIALS COMPLYING WITH THE DOC FF-1
 ?PILL TEST? (CPSC 16 CFR, PART 1630) ARE PERMITTED IN
 ANY AREA WHERE CLASS II MATERIALS ARE REQUIRED.
  
  
  