2013-07-18 17:31:57BUILDING REVISION COMMENTS.
 CODE: 2010 FBC
  
 1- PROVIDE COMPLETE ENGINEERED WALL PANEL ASSEMBLY
 SIGNED AND SEALED (ORIGINAL- 2 COPIES) BY THE ENGINEER
 RESPONSIBLE FOR THE DESIGN.
 ***NOTE; PLEASE MAKE SURE ENGINEER PROVIDES ALL HIS/HER
 INFORMATION. CHAPTER 471 FLORIDA STATUTE.
  
 2- ENGINEERED WALL SYSTEM TO PROVIDE ALL THE DESIGN
 INFORMATION REQUIRED BY SEC. R301.1. SEE ENGINEER OF
 RECORD DESIGN CRITERIA SHOWN ON PLANS.
  
 3- WALL PANEL ASSEMBLY INSTRUCTIONS SUBMITTED REQUIRES
 ENGINEER OF RECORD TO PROVIDE THE WALL ANCHORING
 SPACING FOR THE ANCHORS TO THE CONCRETE SLAB. ENGINEER
 OF RECORD TO PROVIDE INFORMATION. SEC. 107.2.1.3 CITY
 AMENDMENTS TO FBC.
  
 4- WALL PANEL ASSEMBLY INSTRUCTIONS SPECIFY THREE
 DIFFERENT ANCHOR SIZES FOR PANEL TO PANEL ATTACHMENT.
 PROVIDE SPECIFIC SIZE REQUIRED ACCORDING TO THE
 SPECIFIED DESIGN CRITERIA. SEC. 107.2.1.3 CITY
 AMENDMENTS.
  
 5- PROVIDE COMPLETE DETAILS AND SPECS FOR THE
 ATTACHMENT OF GABLE END TRUSSES TO THE WALL PANEL. SEC.
 107.2.1.3 CITY AMENDMENTS TO FBC.
  
 6- REVISED WALL PANEL ASSEMBLY TO BE REVIEWED BY THE
 ENGINEER OF RECORD PRIOR TO SUBMITTAL. SEC. 107.3.4.1
 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712