2013-07-18 17:31:57 | BUILDING REVISION COMMENTS. |
| CODE: 2010 FBC |
| |
| 1- PROVIDE COMPLETE ENGINEERED WALL PANEL ASSEMBLY |
| SIGNED AND SEALED (ORIGINAL- 2 COPIES) BY THE ENGINEER |
| RESPONSIBLE FOR THE DESIGN. |
| ***NOTE; PLEASE MAKE SURE ENGINEER PROVIDES ALL HIS/HER |
| INFORMATION. CHAPTER 471 FLORIDA STATUTE. |
| |
| 2- ENGINEERED WALL SYSTEM TO PROVIDE ALL THE DESIGN |
| INFORMATION REQUIRED BY SEC. R301.1. SEE ENGINEER OF |
| RECORD DESIGN CRITERIA SHOWN ON PLANS. |
| |
| 3- WALL PANEL ASSEMBLY INSTRUCTIONS SUBMITTED REQUIRES |
| ENGINEER OF RECORD TO PROVIDE THE WALL ANCHORING |
| SPACING FOR THE ANCHORS TO THE CONCRETE SLAB. ENGINEER |
| OF RECORD TO PROVIDE INFORMATION. SEC. 107.2.1.3 CITY |
| AMENDMENTS TO FBC. |
| |
| 4- WALL PANEL ASSEMBLY INSTRUCTIONS SPECIFY THREE |
| DIFFERENT ANCHOR SIZES FOR PANEL TO PANEL ATTACHMENT. |
| PROVIDE SPECIFIC SIZE REQUIRED ACCORDING TO THE |
| SPECIFIED DESIGN CRITERIA. SEC. 107.2.1.3 CITY |
| AMENDMENTS. |
| |
| 5- PROVIDE COMPLETE DETAILS AND SPECS FOR THE |
| ATTACHMENT OF GABLE END TRUSSES TO THE WALL PANEL. SEC. |
| 107.2.1.3 CITY AMENDMENTS TO FBC. |
| |
| 6- REVISED WALL PANEL ASSEMBLY TO BE REVIEWED BY THE |
| ENGINEER OF RECORD PRIOR TO SUBMITTAL. SEC. 107.3.4.1 |
| CITY AMENDMENTS. |
| |