2013-08-23 18:19:05RESIDENTIAL (R3) ADDITION, SECOND CHECKLIST.
 CODE: 2010 FBC.
  
 1- REVISE ENERGY CALCULATIONS TO MATCH PLANS:
 A) AREA WEIGHTED AVERAGE OVERHANG DEPTH ON ITEM #7 IS
 NOT 2.00FT.
 B) SPECIFY THE SEER FOR THE PTAC UNIT.
 C) SPECIFY THE HEATING ON ITEM #13.
 D)REVISE ROOF. MATERIAL IS NOT SHINGLES AND ROOF AREA
 IS INCORRECT.
 E)REVISE ORIENTATION FOR WALLS, DOORS AND WINDOWS. SEE
 VICINITY PLAN FOR CORRECT ORIENTATION.
  
 2- REVISE NORTH ARROW SHOWN ON THE SITE PLAN. SEE
 VICINITY MAP ON SAME SHEET FOR CORRECT ORIENTATION.
 ENERGY CALCULATIONS WERE WRONG BECAUSE OF THIS.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS, DETAILS AND SECTIONS.
 B) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 4- SHEET S-2. REVISE THE DESIGN WIND PRESSURES CHART:
 A) REVISE WINDOW/DOOR DESIGN PRESSURES TO CORRESPOND TO
 EXPOSURE "C".
 B) REVISE SLOPED ROOF DESIGN PRESSURES FOR ROOF ZONE 3
 TO CORRESPOND TO EXPOSURE "C".
 C) REVISE THE DIMENSIONS FOR ROOF ZONES 2 AND 3 FOR
 PITCHED AND FLAT ROOF. NEED 4'-0" MIN. SEE NOTE "A" ON
 FIGURE R301.2(7).
  
 5- REVISE NAILING ZONE SPECIFICATIONS ON SHEET S-2:
 A) NEED TO SPECIFY 8D RING SHANK NAILS. SEC.
 R803.2.3.1.
 B) SEE FIGURE R803.2.3.1 FOR DIMENSION OF ROOF ZONE #3.
 GABLE END IS THE ROOF ZONE 3 AND THE MINIMUM DIMENSION
 IS 5'-0".
  
 6- TYP. ADDITION SECTION ON SHEET S-2:
 A) REVISE THE LOCATION OF THE CEILING INSULATION. IT
 CAN'T BE BLOCKING THE SOFFIT VENT. SEC. R806.3.
  
 B) A MINIMUM OF 1" SPACE SHALL BE PROVIDED BETWEEN THE
 INSULATION AND THE ROOF SHEATHING AND AT THE LOCATION
 OF THE VENT. THE 1 X 2 FURRING SHOWN ON THE TYPICAL
 WALL SECTION DOESN'T COMPLY WITH SEC. R806.3. REVISE AS
 REQUIRED.
  
 7- FLAT ROOF FRAMING PLAN:
 A) SPECIFY 8D RING SHANK NAILS. SEC. R803.2.3.1.
  
 B) CROSS VENTILATION IS BLOCKED BY THE 2X10 BLOCKING
 SHOWN ON ROOF FRAMING PLAN AND BY THE (3)2X10 BEAM.
 SEC. R806.1.
  
 8- NEW RIDGE VENT DETAIL SHOWN ON SHEET S-2:
 A) PROVIDE PRODUCT APPROVAL FOR THE RIDGE VENT AS
 REQUIRED BY DCA RULE 9N-3. AND, ARCHITECT TO REVIEW AND
 APPROVE IN WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 B) DETAIL CALLS FOR "TILE ROOF". PRODUCT APPROVAL
 SUBMITTED IS FOR METAL ROOF. REVISE AS REQUIRED TO
 MATCH.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH ITEM
 TO EXPEDITE THE REVIEW PROCESS.
  