Plan Review Notes For Permit 13070464 |
Permit Number |
13070464 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-07-15 10:33:49 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE TAMKO MODIFIED ROOF SYSTEM ON PAGE 13 OF NOA | | NO.12-0716.18 HAS A MAXIMUM EDESIGN PRESSURE OF -52.5 | | PSF. THIS PRESSURE IS TOO LOW FOR THE PERIMETER AND | | CORNER AREAS OF THE ROOF. SUBMIT TWO SETS OF SIGNED AND | | SEALED RAS 117 CALCULATIONS FOR ENHANCED FASTENING AS | | SPECIFIED IN LIMITATION NUMBER 7 ON PAGE 15 OF THE NOA. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|