Plan Review Notes
Plan Review Notes For Permit 13070453
Permit Number 13070453
Review Stop B
Sequence Number 2
Notes
Date Text
2013-07-19 12:05:522010 FBC
  
 1) THE RAS 117 CALCULATIONS SPECIFY 1" THICK
 ENERGYGUARD INSULATION AND A 1:3 SQFT FASTENER DENSITY.
 THE MINIMUM THICKNESS FOR THIS FASTENER DENSITY IS
 1.3". PLEASE CORRECT.
  
 2) IT APPEARS THAT THE ENGINEER USED A FASTENER SPACING
 OF 1.3 SQFT PER FASTENER RATHER THAN 1 FASTENER PER 3
 SQFT. THEREBY SUBSTANTIALLY INCREASING THE NUMBER OF
 FASTENERS PER BOARD. PLEASE REVIEW CALCULATIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW