Plan Review Notes For Permit 13070453 |
Permit Number |
13070453 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-07-19 12:05:52 | 2010 FBC | | | | 1) THE RAS 117 CALCULATIONS SPECIFY 1" THICK | | ENERGYGUARD INSULATION AND A 1:3 SQFT FASTENER DENSITY. | | THE MINIMUM THICKNESS FOR THIS FASTENER DENSITY IS | | 1.3". PLEASE CORRECT. | | | | 2) IT APPEARS THAT THE ENGINEER USED A FASTENER SPACING | | OF 1.3 SQFT PER FASTENER RATHER THAN 1 FASTENER PER 3 | | SQFT. THEREBY SUBSTANTIALLY INCREASING THE NUMBER OF | | FASTENERS PER BOARD. PLEASE REVIEW CALCULATIONS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|