Plan Review Notes For Permit 13070453 |
Permit Number |
13070453 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-07-15 12:22:19 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE. CITY | | AMENDMENTS 107.2.1 | | | | 2) FROM THE GAF NOA NO. 09-0224.01, SPECIFY WHICH ONE | | OF THE APPROVED SYSTEMS, FASTENING OPTION AND MAXIMUM | | DESIGN PRESSURE WILL BE USED. FBC 1609.5.2 | | | | 3) THE DESIGN PRESSURES THAT ARE LISTED IN THE NOA ARE | | TOO LOW FOR THE PERIMETER AND CORNER AREAS OF THE ROOF. | | SUBMIT TWO COPIES OF SIGNED AND SEALED RAS 117 | | CALCULATIONS FOR ENHANCED FASTENING REQUIREMENTS FOR | | THE INSULATION AND BASE SHEET AT THE CORNER AND | | PERIMETER AREAS AS SPECIFIED IN LIMITATION NUMBER 7 ON | | PAGE 31. FBC 1609.5.2 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|