2013-09-26 17:22:06ADDED AS PROVISOS ON PLANS:
 ENGINEERED LETTER FOR WINDLOAD CERTIFICATION REQUIRED
 BY FIRST INSPECTION
 POLE BASES ARE SPECIFIED TO BE DETERMINED BY BY
 STRUCTURAL ENGINEER - PROVIDE DETERMINATION FOR
 INSPECTION
 ALL FIXTURES AND COMPONENTS TO BE LISTED FOR THE USE
 AND USED WITHIN THEIR RESPECTIVE LISTING
 NOTE 3 ON 2A SE-1 IS CONFUSING. IT ADDRESSES A 39 FOOT
 POLE BEING CUT TO 32'AND THE LISTED POLES ARE 35' AND
 25'
 PROVIDE SEPARATION OF CAMERA, NETWORK, PHONE AND OTHER
 WIRING FROM POWER IN THE POLE (FOUND NOTE ON PLANS)
  
  