Plan Review Notes
Plan Review Notes For Permit 13070333
Permit Number 13070333
Review Stop E
Sequence Number 1
Notes
Date Text
2013-07-29 15:19:06PROVIDE CONDUCTORS FOR 200 AMP (310.15). PANEL TO BE
 RATED 200 AMP OR PROVIDE OVERCURRENT THAT COINCIDES
 WITH PANEL RATING (408.36). PROVIDE INTERSYSTEM BONDING
 POINT PER 250.94. PROVIDE LOAD CALCULATION AND LOADS
 PER PANEL.
  