Plan Review Notes For Permit 13070333 |
Permit Number |
13070333 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-07-29 15:19:06 | PROVIDE CONDUCTORS FOR 200 AMP (310.15). PANEL TO BE | | RATED 200 AMP OR PROVIDE OVERCURRENT THAT COINCIDES | | WITH PANEL RATING (408.36). PROVIDE INTERSYSTEM BONDING | | POINT PER 250.94. PROVIDE LOAD CALCULATION AND LOADS | | PER PANEL. | | |
|