2013-08-12 10:20:42FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 GENERAL NOTE:
 PAGE 177 THE ELKAY BOTTLE FILLING STATION LZWSMDK DOES
 NOT APPEAR TO MEET THE REQUIREMENTS OF FBC
 ACCESSIBILITY 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 602.6 WATER FLOW.
 THE SPOUT SHALL PROVIDE A FLOW OF WATER 4 INCHES (100
 MM) HIGH MINIMUM AND SHALL BE LOCATED 5 INCHES (125 MM)
 MAXIMUM FROM THE FRONT OF THE UNIT. THE ANGLE OF THE
 WATER STREAM SHALL BE MEASURED HORIZONTALLY RELATIVE TO
 THE FRONT FACE OF THE UNIT. WHERE SPOUTS ARE LOCATED
 LESS THAN 3 INCHES (75 MM) OF THE FRONT OF THE UNIT,
 THE ANGLE OF THE WATER STREAM SHALL BE 30 DEGREES
 MAXIMUM. WHERE SPOUTS ARE LOCATED BETWEEN 3 INCHES (75
 MM) AND 5 INCHES (125 MM) MAXIMUM FROM THE FRONT OF THE
 UNIT, THE ANGLE OF THE WATER STREAM SHALL BE 15 DEGREES
 MAXIMUM.
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS.
 SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 1. PAGE 059 FITNESS BUILDING & 064 SPA BUILDING: A
 UNISEX TOILET ROOM WILL BE REQUIRED
 403.5 UNISEX TOILET AND BATHING ROOMS.
 IN ASSEMBLY AND MERCANTILE OCCUPANCIES, AN ACCESSIBLE
 UNISEX TOILET ROOM SHALL BE PROVIDED WHERE AN AGGREGATE
 OF SIX OR MORE MALE AND FEMALE WATER CLOSETS IS
 REQUIRED. IN BUILDINGS OF MIXED OCCUPANCY, ONLY THOSE
 WATER CLOSETS REQUIRED FOR THE ASSEMBLY OR MERCANTILE
 OCCUPANCY SHALL BE USED TO DETERMINE THE UNISEX TOILET
 ROOM REQUIREMENT. IN RECREATIONAL FACILITIES WHERE
 SEPARATE-SEX BATHING ROOMS ARE PROVIDED, AN ACCESSIBLE
 UNISEX BATHING ROOM SHALL BE PROVIDED. FIXTURES LOCATED
 WITHIN UNISEX TOILET AND BATHING ROOMS SHALL BE
 INCLUDED IN DETERMINING THE NUMBER OF FIXTURES PROVIDED
 IN AN OCCUPANCY.
  
 2. PAGE 185: PLEASE ADD THE FOLLOWING INFORMATION:
 GAS PERMIT APPLICATION REQUIREMENTS:
  
 2A. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 2B. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2007 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
  
 2C. EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE TO BE BELOW
 CEILING. MANUAL SHUT OFF VALVE TO BE UPSTREAM. UNION TO
 BE DOWN STREAM OF MANUAL VALVE.
  
 3. PAGE 191 FITNESS:
 SEE PLAN FOR VENTING REQUIREMENT 901.2.1
  
 4. PAGE 192 POOL BLDG.:
 SEE PLAN FOR VENTING REQUIREMENTS 905.4 & 911.2
  
 5. PAGE 193 POOL BLDG:
 SEE PLAN FOR HOSE BIBB / WALL HYDRANT REQUIREMENT 606.2
  
 6. PAGE 194 SPA:
 SEE PLAN FOR VENTING REQUIREMENT 901.2.1
  
 7. PAGE 197 & 059 THE ELEVATOR IS REQUIRED TO DRAIN TO
 THE SANITARY INDIRECTLY.
 CITY ORD. SEC. 90-203 PROHIBITED DISCHARGES; ILLICIT
 CONNECTIONS
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  
  