Review Stop E
Sequence Number 1
Notes
Date Text
2013-07-10 14:22:0313070254
 701 57TH STREET
 NEW ELECTRIC SERVICE
  
 THE SCOPE OF THE PROPOSED ELECTRICAL WORK IS NOT CLEAR.
 THE PROPERTY IS SHOWN AS A SINGLE FAMILY AND NOT A TWO
 FAMILY.
  
 PROVIDE A DETAILED ELECTRICAL PLAN WHICH SHOWS THE
 CONDUIT AND CONDUCTORS FEEDING EACH UNIT. NEC 215.5
  
 SHOW LOCATION OF SERVICE AND MAINS. MAIN DISCONNECTS
 MUST BE SERVICE RATED, WEATHER RESISTANT IF LOCATED
 OUTSIDE AND GROUPED IN ONE LOCATION. NEC 110.20,
 230.66, 230.79, 230.71
  
 GROUNDING AND BONDING OF PANEL BOARDS AT SEPARATE
 BUILDINGS SHALL INCLUDE AN EQUIPMENT GROUNDING
 CONDUCTOR AND A GROUNDING ELECTRODE. NEC 250.32 (A) AND
 (B)
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS. FBC R313
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  
  