Plan Review Notes For Permit 13070239 |
Permit Number |
13070239 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-08-15 10:20:18 | BUILDING PROVISO: | | FLOOR/ CEILING ASSMBLIES WITH THROUGH PENETRATIONS WILL | | REQUIRE FIRE STOP SYSTEMS: | | 2010 FBC-B 713.4.1.1.2 THROUGH-PENETRATION FIRESTOP | | SYSTEM. | | THROUGH PENETRATIONS SHALL BE PROTECTED BY AN APPROVED | | THROUGH-PENETRATION | | FIRESTOP SYSTEM INSTALLED AND TESTED IN ACCORDANCE WITH | | ASTM E 814 OR UL 1479, | | WITH A MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 | | INCH OF WATER (2.49 PA). | | THE SYSTEM SHALL HAVE AN F RATING/T RATING OF NOT LESS | | THAN 1 HOUR BUT NOT LESS | | THAN THE REQUIRED RATING OF THE FLOOR PENETRATED. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] |
|