2013-07-16 07:17:18 | BUILDING PLAN REVIEW |
| PERMIT: 13070239 |
| ADD: 513 CLEMATIS ST |
| CONT: L B ROWE |
| TEL: (561)635-8227 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: JULY 16/2013 |
| ACTION: DENIED |
| |
| 1) NO BUILDING OR ARCHITECTURAL PLANS WERE SUBMITTED |
| ,INDICATING EXTISTING CONDITIONS AND THE NEW PROPOSED |
| WORK. 2010 AMENDMENTS TO FLORIDA BUILDING CODE, CHAPTER |
| 1, ADMINISTRATION, WPB. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE |
| DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| ELECTRONIC MEDIA DOCUMENTS SHALL BE |
| SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN |
| DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS |
| CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| THE BUILDING OFFICIAL MAY |
| ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS |
| FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE |
| CONFORMITY TO ITS RECORD RETENTION PROGRAM. |
| |
| 2) THE DESIGNER OF RECORD SHALL PRINT THEIR NAME, SIGN |
| THEIR NAME AND LICENSE NUMBER TO THEIR DESIGNED WORK |
| AAND WITHIN THE SCOPE OF THEIR LICENSE, NO BUILDING OR |
| ARCHITECTURAL PLANS WERE SUBMITTED. 107.1. |
| |
| 3) SCOPE OF WORK, THE ELECTRICAL PLANS INDICATE WORK AT |
| BOTH 513 & 515 IT IS ASSUMED CLEMATIS? PLEASE IDENTIFY |
| WHERE THE WORK IS GOING TO TAKE PLACE ON THE PLANS FOR |
| JOBSITE VARIFICATION. 2010 FBC 501.2. ADDRESS |
| IDENTIFICATION. |
| |
| 4) THE PROPERTY APPRIAERS WEB SITE INDICATE A TWO STORY |
| AS WELL AS A ONE STORY BUILDING. THE 2ND STORY BUILDING |
| INDICATES A RESIDENTIAL UNIT ABOVE, PLEASE PROVIDE |
| COMPLIANCE WITH 2010 FBC-B 707.3.9 & TABLE 707.3.9 2HR/ |
| NON SPRINKLERED BUILDINGS. |
| |
| 5) 2010 ADMINISTRATIVE CODE 107.3.5 MINIMUM PLAN REVIEW |
| CRITERIA FOR BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 1 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING |
| OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA |
| AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FLOOR/ROOF |
| FRAMING PLAN: |
| 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| SHALL BE DETERMINED. |
| 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| (SEE TABLE 503). |
| 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL |
| INCLUDE THE FOLLOWING COMPONENTS: |
| FIRE-RESISTANT SEPARATIONS |
| FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE |
| RESISTANCE |
| 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| EARLY WARNING SMOKE EVACUATION SYSTEMS |
| SCHEMATIC FIRE SPRINKLERS |
| STANDPIPES |
| PRE-ENGINEERED SYSTEMS |
| RISER DIAGRAM |
| 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL |
| INCLUDE THE FOLLOWING |
| REQUIREMENTS: |
| OCCUPANT LOAD AND EGRESS CAPACITIES |
| 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| OCCUPANCY LOAD |
| GROSS |
| NET |
| MEANS OF EGRESS |
| EXIT ACCESS |
| EXIT |
| EXIT DISCHARGE |
| STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION |
| DOORS |
| EMERGENCY LIGHTING AND EXIT SIGNS |
| 8. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE |
| FOLLOWING: |
| SITE REQUIREMENTS |
| ACCESSIBLE ROUTE |
| VERTICAL ACCESSIBILITY |
| TOILET AND BATHING FACILITIES |
| DRINKING FOUNTAINS |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |