Plan Review Notes For Permit 13070174 |
Permit Number |
13070174 |
|
Review Stop |
M |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2013-12-11 17:11:21 | RESIDENTIAL (R3) GARAGE CONVERSION, FIFTH MECHANICAL | | REVIEW CHECKLIST. | | CODE: 2010 FBC. | | | | 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS. | | COMPLETE CALCULATIONS NEED TO BE DONE BASED ON THE | | BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION OF THE | | BUILDING AS REQUIRED BY SEC. 403.6.1 OF 2010 FBC-ENERGY | | CONSERVATION. ALSO, NEED TO SHOW THE MANUFACTURER AND | | MODEL NUMBERS (INDOOR AND OUTDOOR). | | | | ***REPEAT COMMENT. CALCULATIONS WERE NOT SUBMITTED | | | | 2- BEDROOM TO SHOW COMPLIANCE WITH THE RETURN AIR AND | | BALANCED RETURN AIR REQUIREMENTS OF SEC. R1602 OF 2010 | | FBC-RESIDENTIAL. (REPEAT COMMENT). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|