2013-12-04 13:46:232010 FBC / 2008 NEC
  
 DENIED BY ELECTRICAL
  
 1) THE ENGINEER'S SEAL ON THE DRAWINGS IS NOT
 ACCEPTABLE. SEE 61G15-23.001 SEALS ACCEPTABLE TO THE
 BOARD. HTTPS://WWW.FLRULES.ORG/GATEWAY/RULENO.ASP?ID=61
 G15-23.001
 THIS COMMENT HAS NOT YET BEEN ADDRESSED.
  
 2) THE RESUBMITED PLAN IS MISSING THE FOLLOWING
 INFORMATION THAT WAS ADDRESSED ON THE PREVIOUS PLAN
 SUBMITTAL:
  
 2.1) THE 150 AMP SUB-PANEL REQUIRES (3) #1/0 THW CU
 CONDUCTORS AND A #6 GROUND WIRE IN 1-1/2" CONDUIT. NEC
 TABLE 310.16, TABLE 250.66 AND ANNEX C TABLE C.1
  
 2.2) SHOW COMPLIANCE WITH NEC 250.94 FOR INTER-SYSTEM
 BONDING REQUIREMENT.
  
 2.3) REVISE GENERAL ELECTRICAL NOTE THAT GFCI ARE
 REQUIRED WITHIN 6 FEET OF THE SINK. 2008 NEC 210.8 (A)
 (6) REQUIRES ALL RECEPTACLES INSTALLED TO SERVE KITCHEN
 COUNTER TOPS TO BE GFCI.
  
 2.4) THE RECEPTACLE LOCATED IN THE ATTACHED UTILITY
 SHED IS REQUIRED TO BE GFCI PROTECTED. NEC 210.8 (A)
 (2)
  
 2.5) SHOW COMPLIANCE WITH FBC 314 .3.1 FOR REQUIRED
 SMOKE ALARMS.
  
 2.6) SHOW COMPLIANCE WITH NEC 210.52 (E) (1) FOR
 REQUIRED OUTDOOR OUTLETS AT THE FRONT AND BACK OF THE
 DWELLING.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]