Plan Review Notes For Permit 13070174 |
Permit Number |
13070174 |
|
Review Stop |
E |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2013-12-04 13:46:23 | 2010 FBC / 2008 NEC | | | | DENIED BY ELECTRICAL | | | | 1) THE ENGINEER'S SEAL ON THE DRAWINGS IS NOT | | ACCEPTABLE. SEE 61G15-23.001 SEALS ACCEPTABLE TO THE | | BOARD. HTTPS://WWW.FLRULES.ORG/GATEWAY/RULENO.ASP?ID=61 | | G15-23.001 | | THIS COMMENT HAS NOT YET BEEN ADDRESSED. | | | | 2) THE RESUBMITED PLAN IS MISSING THE FOLLOWING | | INFORMATION THAT WAS ADDRESSED ON THE PREVIOUS PLAN | | SUBMITTAL: | | | | 2.1) THE 150 AMP SUB-PANEL REQUIRES (3) #1/0 THW CU | | CONDUCTORS AND A #6 GROUND WIRE IN 1-1/2" CONDUIT. NEC | | TABLE 310.16, TABLE 250.66 AND ANNEX C TABLE C.1 | | | | 2.2) SHOW COMPLIANCE WITH NEC 250.94 FOR INTER-SYSTEM | | BONDING REQUIREMENT. | | | | 2.3) REVISE GENERAL ELECTRICAL NOTE THAT GFCI ARE | | REQUIRED WITHIN 6 FEET OF THE SINK. 2008 NEC 210.8 (A) | | (6) REQUIRES ALL RECEPTACLES INSTALLED TO SERVE KITCHEN | | COUNTER TOPS TO BE GFCI. | | | | 2.4) THE RECEPTACLE LOCATED IN THE ATTACHED UTILITY | | SHED IS REQUIRED TO BE GFCI PROTECTED. NEC 210.8 (A) | | (2) | | | | 2.5) SHOW COMPLIANCE WITH FBC 314 .3.1 FOR REQUIRED | | SMOKE ALARMS. | | | | 2.6) SHOW COMPLIANCE WITH NEC 210.52 (E) (1) FOR | | REQUIRED OUTDOOR OUTLETS AT THE FRONT AND BACK OF THE | | DWELLING. | | | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|